Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル

ページ / 258
SDC / DHC 
Hydraulic Components 
EN2H-0221GE51 R0808 
149 
Besides return temperature limitation either volume flow limit or 
thermal output limit can also be set for this controller. The 
selection of these functions is described below in parameter 11. 
Para-
meter 
Designation 
Range  
Pre-
setting 
Step 
Unit 
08 Max. 
return 
setpoint 
0 ... 100  90 
0.5 
°C 
09 Starting 
point 
of the flexible 
district heating 
return 
temperature 
Off 
–40...+10
Off 0.5 
°C 
11 Return 
limit 
0 = 
Temperature 
1 = Volume 
flow and 
temperature 
2 = Heat output 
and 
temperature 
0 / 1 / 2 
 
7.2.4  Return temperature limit for hot-water loading  
In the case of hot-water loading a special constant return setpoint 
applies. It is valid only if the hot-water loading pump is operating. 
The return setpoint is to be set with parameter 10.  
Para-
meter
 
Designation 
Range  
Presetti
ng
 
Step 
Unit 
10 Hot-water 
circuit loading: 
Target return 
40 ... 100  90 
0.5 
°C