2.6  Safety precautions for EMC-compliant installation  
Mains lines and sensor/data bus lines must be installed separate 
from each other. A minimum of 2 cm space must be present 
between the lines. It is permissible to cross lines. 
x
a
b
y
ç
é
æ
 
a  Mains 230 V AC 
x  15 cm 
b  Data bus line 12 V AC 
y  2 cm 
For control devices with their own mains connection, separate 
installation of mains and sensor/bus lines must absolutely be 
ensured. If cable ducts are used, they are to be provided with cut-
off bridges.