Hydraulic Components 
SDC / DHC  
152 EN2H-0221GE51 
R0808 
Legend: 
t
setpoin
HWPC
 = Actual temperature at flow sensor "hot-water pre-
control" 
t
setpoin
HW
 = Hot-water setpoint temperature 
)
(
09 HW
P
= Value of parameter 09 (hot-water loading temperature 
offset) 
HW
SD
= Switching difference hot water 
 
Both pumps (tank loading pump and hot-water pre-control) switch 
off after completion of a hot-water circuit loading, taking into 
account their extended running times. If they are to switch off 
simultaneously, identical extended running times must be 
selected for them. 
 
7.2.7  Quick hot-water control  
For monetary reasons, hot-water tanks are not used in many 
district heating systems, especially in Eastern Europe. The hot-
water setpoint temperature is held in a closed loop pipeline here 
(see hydraulic example). 
MK
SF
VF
SLP
b
a
 
a  Flow from closed loop 
pipeline 
b Draw-off 
points 
 
•  Minimum spread between the tank sensor and the return 
sensor from which an offset at the valve is given (see "Mixed 
Heating Circuit 1"/"Mixed Heating Circuit 2" menu, parameter 
39) 
•  Additional value for offset in %/K deviation (valve staring point 
for controller) (see "Mixed Heating Circuit 1"/"Mixed Heating 
Circuit 2" menu, parameter 40) 
 
New parameters