Hydraulic Components 
SDC / DHC  
194 EN2H-0221GE51 
R0808 
Tank parallel operation (combined operation: hot-water 
loading/heating) 
WEZ1
WEZ2
WEZ3
WEZ4
WEZ5
10s
10s
1min
1min
2min
2min
2min
2min
 
 
•  Connection up to the stage of parameter 09 with minimum 
delay for hot-water loading 
•  In case of further need via heating, further connection with 
configured delay of parameter 02 
•  Reversion with configured delay parameter 03 
 
7.3.5.2  Circulation pump (CIR.)  
This function is only available, if a variable output is assigned to a 
circulation pump 
 
The output controls a hot-water circulation pump. 
 
The use of the economy interval minimises the usual circulation 
losses owing to adjustable switch-on intervals during operation 
and determines the standstill time of the hot-water circulation 
pump within an adjustable period (economy interval).  
 
This parameter determines the length of the period and hence the 
duration of the pause in a circulation pump pulse operating mode. 
Economy interval 
Pause
 = Economy interval 
Period duration
 - Economy 
interval 
Pulse
 
The switching-on degree is calculated from the ratio:  
n = Pulse time/Period duration x 100 (%) 
Example: 
With an standstill time of 15 min. and a period of 20 min., the 
circulation pump will run for 5 min. before the subsequent pause 
of 15 min. 
The following is used to calculate the switching-on degree:  
n = 5/20 = 25% 
 
In this function a hot-water circulation pump can be coupled to an 
existing automatic program of a control circuit with regard to the 
NOTE
Function
Economy interval 
(pulse) 
Economy interval 
(period duration) 
Switching times