Hydraulic Components 
SDC / DHC  
234 EN2H-0221GE51 
R0808 
7.3.12.3  Mode of operation of cascade control 
7.3.12.3.1 Switch-on 
characteristics 
The switch-on characteristics of the boiler stages are determined 
by the set switching differential and the dynamic switch-on delay. 
The stage number is incremented only when the following criteria 
are fulfilled: 
 
BT
ACTUAL
 < BT
SETPOINT
 – SD/2 
 
 
t >= t
Switch-on delay
 * (100 – (dVT * 100 / VLSetpoint) ) / 100  
 
Stages
Number 
= Stages
Selection
 
 
The boiler temperature of the leading boiler or the total flow 
sensor must have exceeded the specified boiler setpoint minus 
half of the switching differential (switch-on delay time) for at least 
the calculated switch-on delay. Additionally, the requested stage 
number must have been sent to central device 10 as the active 
status response. 
 
7.3.12.3.2 Switch-off characteristics 
The stage number is decreased again as soon as the temperature 
of the leading boiler or of the total flow sensor exceeds the 
present setpoint boiler temperature plus half of the switching 
differential for at least the calculated switch-off delay time. 
 
BT
ACTUAL
 > BT
SETPOINT
 – SD/2 or BT
ACTUAL
 >= BT
MAX
  
 
t >= t
Switch-on delay
 * (100 – (dVT * 100 / VLSetpoint) ) / 100  
 
Stages
Number 
= Stages
Selection