Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル

ページ / 258
SDC / DHC 
Operation 
EN2H-0221GE51 R0808 
89 
5.4.3  "Hot-water circuit" menu (DHW) 
This menu contains all parameters required to program the  
hot-water circuit, except the switch time programs. 
 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
Hot 
water 
Hot water at night 
10°C to normal hot-water 
temperature 
40  
OFF 
No legionella protection  OFF 
 
Mon to 
Sun 
Legionella protection on 
specified day of week 
 
 
Legio 
protect
ion day 
Legionella 
protection day 
ALL Legionella 
protection 
every day 
 
 
03 Legionella 
protection time 
00:00 ... 23:00 hours 
02:00 
 
04 Legionella 
protection 
temperature 
10 °C to setting value of 
parameter 06  
65  
1 Hot-water 
circuit 
temperature sensor 
1  
05 
Transducer for hot-
water circuit 
2 Hot-water 
circuit 
temperature controller 
(thermostat) 
 
 
06 Maximum 
temperature limit 
for hot water circuit 
20°C to heat generator maximum 
temperature 
If parameter 07 = 7:  
20 to 90°C. 
In automatic mode, from hot-
water circuit minimum 
temperature. 
65