Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル

ページ / 258
SDC / DHC 
Operation 
EN2H-0221GE51 R0808 
99 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
Heat-
ing 
circuit 
name 
Heating circuit 
name 
00000 ... ZZZZZ 
– 
 
 
* OEM 
 
 
5.4.6  "Heat generator" menu (HEAT GENER. 
The parameters in this menu refer to the type of the respective 
heat generator and the associated specific control functions. 
 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
OFF 
Without heat generator 
 
Oil/gas - one stage 
 
 
Oil/gas - two stages 
 
 
Oil/gas - 2 x one stage 
 
 
4 Modulating 
burner   
 
01 Design 
5 Open 
Therm 
 
 
OFF 
No start-up protection 
 
1 Unlimited 
start-up 
protection 
 
 
2 Start-up 
protection 
controlled by weather 
conditions 
 
 
02 Start-up 
protection 
(not if parameter 
01 = OFF) 
3 Start-up 
protection 
disconnected 
 
 
03 Minimum 
tem-
perature limit (not 
if parameter 01 = 
OFF) 
5°C to setting value of parameter 
04 
38 (5 with 
automatic 
operation)  
 
04 Maximal 
temperature limit 
(not if parameter 
01 = OFF) 
Setting value of parameter 03 to 
setting value of parameter 30 
(OEM maximum limit) 
80