Desa HDR26PT ユーザーズマニュアル

ページ / 56
www.desatech.com
11
121255-01A
3.  Align holes in base foot with mounting holes 
on bottom of cabinet (see Figure 13).
4.  Secure  base  foot  to  heater  using  sheet 
metal screws.
5.  Repeat for other side.
INSTALLATION
Continued
Figure 14 - External Regulator With Vent 
Pointing Down
External 
Regulator
Propane/LP 
Supply Tank
Vent 
Pointing 
Down
IMPORTANT: For natural gas, check gas line 
pressure before connecting heater to gas line. 
Gas  line  pressure  must  be  no  greater  than 
10.5" of water. If gas line pressure is higher, 
heater regulator damage could occur.
  CAUTION:  For  propane/LP 
gas,  never  connect  heater  di-
rectly to the propane/LP supply. 
This heater requires an external 
regulator  (not  supplied).  Install 
the external regulator between the 
heater and propane/LP supply.
For propane/LP gas, the installer must supply 
an external regulator. The external regulator 
will reduce incoming gas pressure. You must 
reduce incoming gas pressure to between 11" 
and 14" of water. If you do not reduce incom-
ing  gas  pressure,  heater  regulator  damage 
could occur. Install the external regulator with 
the  vent  pointing  down  as  shown  in  Figure 
14.  Pointing  the  vent  down  protects  it  from 
freezing rain or sleet.
  CAUTION:  Use  only  new, 
black  iron  or  steel  pipe.  Inter-
nally-tinned copper tubing may 
be used in certain areas. Check 
your  local  codes.  Use  pipe  of 
large enough diameter to allow 
proper gas volume to heater. If 
pipe is too small, undue loss of 
volume will occur.
Typical Inlet Pipe Diameters
16-18,000 Btu/hr models - 3/8" or greater
26-30,000 Btu/hr models - 1/2" or greater
Installation  must  include  equipment  shutoff 
valve, union and plugged 1/8" NPT tap. Locate 
NPT tap within reach for test gauge hook up. 
NPT tap must be upstream from heater (see 
Figure 15, page 12).
Figure 13 - Installing Base Feet (actual 
heater may vary from illustration)
Sheet 
Metal 
Screw
Wood 
Screw
Base Foot
Mounting Base Feet to Floor
1.  Remove front panel (see Removing Front 
Panel of Heater, page 9).
2.  Position heater with base feet in desired 
location. Mark holes for drilling. Remove 
heater with base.
3.  For carpeted floors, make a small cut with 
a sharp knife at marked locations prior to 
drilling. If mounting  base to a wood floor, 
drill 1/8" diameter hole, 3/4" deep. (Do not 
use anchors in wood floors).
 
If  mounting  base  to  a  concrete  floor,  drill 
with 1/4" diameter concrete drill bit, 1
3
/
8
" into 
floor. Insert anchors completely into holes.
4.  Reposition  heater  with  base  feet  over 
holes.  Secure  base  to  floor  with  wood 
screws. See Figure 13.
CONNECTING TO GAS SUPPLY
  WARNING:  This  appliance 
requires  a  3/8"  NPT  (National 
Pipe Thread) inlet connection to 
the pressure regulator.
 WARNING: A qualified service 
person must connect heater to gas 
supply. Follow all local codes.
 WARNING: For natural gas, never 
connect heater to private (non-util-
ity) gas wells. This gas is commonly 
known as wellhead gas.