*  A CSA design-certified equipment shutoff valve 
with 1/8" NPT tap is an acceptable alternative to 
test gauge connection. Purchase the optional CSA 
design-certified equipment shutoff valve from your 
dealer. See Accessories, page 30.
CHECKING GAS CONNECTIONS
 WARNING: Test all gas piping 
and  connections,  internal  and 
external to unit, for leaks after 
installing or servicing. Correct 
all leaks at once.
Tee Joint
Reducer 
Bushing to 
1/8" NPT
1/8" NPT 
Plug Tap
Test Gauge Connection*
3/8" NPT 
Pipe Nipple
Heater 
Cabinet
Equipment 
Shutoff 
Valve*
3" Min.
Natural Gas
From Gas Meter 
(4" W.C. to 10.5" W.C. 
Pressure)
Propane/LP
From External 
Regulator
(11" W.C. to 14" W.C. 
Pressure)
Ground Joint 
Union
IMPORTANT:
  Hold the pressure regulator with 
wrench when connecting it to gas piping and/or 
fittings. Do not over tighten pipe connection to 
regulator. The regulator body could be damaged.
Tee Joint
Pipe 
Nipple
Cap
Sediment 
T
rap
INSTALLATION
Continued
  WARNING:  Never  use  an 
open flame to check for a leak. 
Apply a noncorrosive leak detec-
tion fluid to all joints. Bubbles 
forming show a leak. Correct all 
leaks at once.
  CAUTION:  For  propane/LP 
gas, make sure external regula-
tor has been installed between 
propane/LP supply and heater. 
See guidelines under 
Connect-
ing to Gas Supply, page 12.
PRESSURE TESTING GAS SUPPLY 
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG 
(3.5 kPa)
1.  Disconnect appliance with its appliance main 
gas  valve  (control  valve)  and  equipment 
shutoff valve from gas supply piping system. 
Pressures in excess of 1/2 psig will damage 
heater regulator.
2.  Cap off open end of gas pipe where equipment 
shutoff valve was connected.
3.  Pressurize  supply  piping  system  by  either 
opening propane/LP supply tank valve for 
propane/LP gas or opening main gas valve 
located on or near gas meter for natural gas 
or using compressed air.
4.  Check all joints of gas supply piping system. 
Apply a noncorrosive leak detection fluid to 
all joints. Bubbles forming show a leak.
5.  Correct all leaks at once.
6.  Reconnect  heater  and  equipment  shutoff 
valve to gas supply. Check reconnected fit-
tings for leaks.
Test Pressures Equal To or Less Than 
1/2 PSIG (3.5 kPa)
1.  Close equipment shutoff valve (see Figure 16).
Figure 15 - Gas Connection
Figure 16 - Equipment Shutoff Valve
Open
Closed
Equipment 
Shutoff Valve
Pressure 
Regulator