TUBULAR UNIT HEATER 
HIGH ALTITUDE DERATION
This Tubular Unit Heater has been manufactured utilizing 
standard burner orifi ces and a normal manifold pressure 
setting as per the specifi cations shown on your unit rating 
plate.
All unit deration must be done through fi eld adjustments 
by a qualifi ed technician. Once the proper adjustments 
are made in the fi eld, attach label #J17-06459 to the unit, 
and record adjusted manifold pressure, altitude of the 
unit installation and the technician’s name and date on 
the label using a permanent marker.
Refer to Installation Instruction section on Adjustments-
Gas Input Rate for adjusting the manifold pressure. 
Manifold 
Pressure
(In. W.C.)
PROPANE (LP) GAS
NATURAL GAS
Heating* 
Value
BTU/Cu. ft.
Altitude
(Feet)
8.6
8.5
8.4
8.4
8.3
8.2
8.1
8.0
7.9
7.7
7.6
7.5
7.4
7.2
7.1
6.9
6.8
  2,000
  2,500
  3,000
  3,500
  4,000
  4,500
  5,000
  5,500
  6,000
  6,500
  7,000
  7,500
  8,000
  8,500
  9,000
  9,500
10,000
*Notes: 
1. Consult local utility for actual heating value.
2. Tables based on heating value of 1,050 BTU/Cu. ft. at sea level.
2,278
2,237
2,196
2,156
2,116
2,077
2,039
2,000
1,964
1,927
1,891
1,853
1,817
1,781
1,745
1,709
1,673
Table 5A
Manifold 
Pressure
(In. W.C.)
Heating* 
Value
BTU/Cu. ft.