Rinnai V3237FFU ユーザーズマニュアル

ページ / 52
39
Rinnai  Corporation
V3237  Models
PRESSURE  RELIEF  VALVE
1)  An approved pressure relief valve should  be  installed  in  all  water  heating  systems. 
2)  The  pressure  relief  valve  must  meet  the  following  criteria: The  relief  valve  must  comply  with 
the  standard  for  Relief  Valves  and Automatic  Gas  Shutoff  Devices  for  Hot  Water  Supply 
Systems ANSI  Z21.  22  and/or  the  standard  CAN1-4.4  Temperature,  Pressure,  Temperature 
and  Pressure  Relief  Valves  and  Vacuum  Relief  Valves.   This  relief  valve  set  point  must  not 
exceed  150  PSI  of  pressure. The  pressure  relief  valve  hourly  Btu  rated  temperature  steam 
discharge  capacity  shall  not  be  less  than  the  hourly  Btu  input  rating  of  the  unit.  Multiple 
valves  may  be  used.
3)  The  relief  valve  should  be  added  to  the  hot  water  outlet  line  per  manufacturer's  instructions. 
DO  NOT  place  any  other  type  valve  or  shut  off  device  between  the  relief  valve  and  the  hot 
water  heater. 
4)  Do not plug the relief valve and do not install any reducing fittings or other restrictions in the relief 
line. The relief line should allow for complete drainage of the valve and the line. 
5)  If  a  relief  valve  discharges  periodically,  this  may  be  due  to  thermal  expansion  in  a  closed 
water  supply  system.    Contact  the  water  supplier  or  local  plumbing  inspector  on  how  to 
correct  this  situation.    Do  not  plug  the  relief  valve.
6)  Should  overheating  occur  or  the  gas  supply  fail  to  shut  off,  turn  off  the  manual  gas  valve  on 
the  Rinnai.
GAS  PRESSURE  CHECK  LIST
1)  Remove  pressure  test  point  screw,  attach  pressure  gauge  to  test  point.   
2)    Turn  on  the  gas  and  power  to  the  water  heater.
3)    Open  any  hot  water  tap  fully. 
4)    Check  test  point  or  supply  pressure  in  water  columns  per  inch  as  shown. 
REU-V3237FFU Series
REU-V3237W Series
Inlet Gas Pressure
6" - 10.5"
6" - 10.5"
Low Fire Manifold Gas Pressure
0.67"
0.65"
High Fire Manifold Gas Pressure
3.0"
2.8"
Natural Gas Inlet and Manifold Gas Pressure by Model
REU-V3237FFU Series
REU-V3237W Series
Inlet Gas Pressure
10" - 13.5"
10" - 13.5"
Low Fire Manifold Gas Pressure
0.83"
0.80"
High Fire Manifold Gas Pressure
3.7"
3.8"
Propane Gas Inlet and Manifold Gas Pressure by Model