Thermo Products OL2-56 ユーザーズマニュアル

ページ / 32
All installations and services must be performed by qualified service personnel. 
 
11 
RIELLO BURNER APPLICATION CHART 
 
The optional F3 and F5 Riello flame retention oil burners have been UL listed (UL File #MP3252) for application on 
the following Thermo Pride oil fired furnaces. 
 
             MODEL 
PART 
OH3 
OC5, OL5, 
OH5, OT5 
OL11, OH11,  
OT11 
OL16, OH16, 
OT16 
OL20 
MTG. PLATE 
PART NO. 
TOP-25752 
BTM-35733 
35750 35750 35750 
35750 
 
MTG. PLATE 
GASKET 
PART NO. 
330090 330088 330088 330088 330088 
**NOZZLE 
    SIZE 
.50-60A  .60-60A* .75-60A* .90-60A* 1.10-60A* 
NOZZLE 
PART NO. 
380393 380394 380395 380396 380397 
OIL PUMP 
PRESSURE 
170 PSI 
145 PSI 
145PSI 
145 PSI 
150PSI 
BURNER 
F3 F3 F5 F5 F5 
BURNER  
PART NO. 
380215 380215 380216 380216 380216 
 
* A refers to hollow pattern nozzle 
** NOTE:  The reason the Riello burner nozzle sizes are smaller than the standard Thermo Pride burner nozzles is 
that pre-set pump pressures are higher, therefore achieving the same firing rate with a smaller nozzle. 
 
For more specific burner information, specifications or service information, reference the training manual enclosed 
with each Riello burner or contact:                     Riello Corporation of America, 
                                                                                    5 Pond Park Road 
                                                                            Hingham, Massachusetts 02043 
                                                                                    (617) 749-8292 
 
 
I.  HEAT EXCHANGER CLEANING INSTRUCTIONS: 
 
?
?
?
?WARNING: THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED 
SERVICE  PERSON. 
 
It is important to inspect and clean the heat exchanger once a year, or as necessary, to remove any build-up of soot. 
A layer of soot on the inside of the heat exchanger will act as an insulator and reduce heat transfer, resulting in less 
efficiency. 
 
To clean the heat exchanger, first turn off all power to the unit. Next, remove the access panel (see below and 
beginning of following page) immediately above the burner (on the horizontal furnace, it will be located to the side 
of the burner) to gain entry to the clean-out covers, refer to figure 15. This panel is identified with a label. Remove 
clean-out covers, the vent connector pipe to the chimney, the burner, and the burner mounting plates. When 
removing the clean-out covers, special care must be taken not to damage the gaskets. Should the gaskets separate, 
crack, break, or be unsuitable for reuse, the gasket must be replaced before reattaching the clean-out covers.