Your  new  furnace  should  provide  many  years  of  trouble  free 
performance, however, a yearly inspection of the burners , flue 
passageways and the outlet vent assembly should be done.  Be 
sure all passageways are open and clear of any obstruction, or soot 
build up.  Be sure to shut off all power to the unit while performing 
this inspection.  
Periodically remove the circulating air filter and clean with water 
to remove all dirt.  Shake dry and reinstall in unit.
System Operation
1.  This furnace has an electronic thermostat and control board 
to monitor the room temperature and then control the furnace 
operation to provide the best comfort and performance from a 
heating appliance.  To operate unit turn ON/OFF switch to ON 
and then turn temperature control knob clockwise slowly till 
furnace turns on.  For typical room comfort, the control knob 
should be pointed toward medium.
2.  The furnace control board follows sequence of operation which 
allows for self diagnosis in the event there is a problem.  The 
control then blinks a status light, a set number of blinks based 
on what problem has been encountered.  When the furnace is 
on and there is a no fault condition, the green LED is on.
  On a typical call for heat by the integral thermostat 24 VAC is 
applied to the W terminal on the board.   
  The inducer blower circuit is energized and the inducer blower 
comes on for 15 seconds pre-purging out any gas and closing 
the pressure switch.
  The hot surface ignitor is energized and after a 17 second warm-
up, the gas valve circuit is energized, opening the gas valve and 
igniting the burners.   After burning for about 30 seconds, the 
circulating air blower comes on, delivering warm air to the room.  
If ignition does not occur, the ignition sequence is repeated again 
up to 2 more times. (3 trials for ignition-total)
3.  After the furnace operates and satisfies the thermostat, the gas 
valve closes and the circulating air blower continues to run for 
about 2 minutes and then shuts off.  The inducer blower runs 
for 5 seconds and shuts off.
  If  for  any  reason  ignition  and  operation  does  not  occur,  the 
control board will blink the green fault status LED, a sequence 
code, indicating what to look for as a troubleshooting guide.   
If the green LED is ON but not blinking check the electronic 
temperature control to verify its operation. This can be easily done 
by disconnecting the 3 electronic temperature control leads from 
the main furnace board and using a pig tail jumper to connect 
R & W together on the board. If the furnace comes on and runs 
normally the temperature control board is malfunctioning. If 
the heater still does not come on, then the main furnace board 
is malfunctioning. Look for any fault codes below and verify 
the 3 amp fuse is not blown.
OPERATION AND TROUBLESHOOTING