Thermo Products CMA2-75N ユーザーズマニュアル

ページ / 55
All installations and services must be performed by qualified service personnel. 
CMA1-50 
 
ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE 
COOLING UNIT 
HTG Speed 
Recommended CLG Speed 
24,000 LOW 
MED-LOW 
 
30,000 LOW 
MED-HIGH 
36,000 LOW HIGH 
 
 
Furnace Airflow (CFM) vs. External Static pressure (in. WC.) 
Speed Tap \ 
Static 
Pressure 
0.1 0.2 0.3 0.4 0.5 0.6  0.7 
Low 
836 805 773 743 695 
620 566 
ML 
1044 1010  972  914  860 826  752 
MH 
1250 1196 1146 1101 1038 977  902 
High 
1339 1338 1283 1233 1162 
1086 1008 
 
 
 
Temperature Rise vs. External Static Pressure (in. WC.) 
Speed Tap \ 
Static 
Pressure 
0.1 0.2  0.3  0.4 0.5 0.6  0.7 
Low 
53 
55 
57 
59 
63 
71 
78 
ML 
42 
44 
45 
48 
51 
53 
59 
MH 
35 37  38  40 
42 
45 
49 
High 
31 33  34  36 38 
41 44 
 
 
 
 
 
 
 
 
 
               
Blower Motor Current Draw (Amps) vs. External Static pressure (in. WC.) 
Speed Tap \ 
Static 
Pressure          
0.1 0.2 0.3 0.4 0.5  0.6  0.7 
Low 
3.3 3.2 3.1 3.0 2.9  2.7  2.6 
ML 
4.0 3.8 3.6 3.5 3.4  3.2  3.1 
MH 
4.6 4.4 4.2 4.1 4.0  3.8  3.6 
High 
5.3 5.1 5.0 4.9 4.7  4.6  4.4 
 
 
Blower Motor Watts vs. External Static pressure (in. WC.) 
Speed Tap \ 
Static 
Pressure 
0.1 0.2  0.3  0.4 0.5 0.6  0.7 
Low 
315 311  304  300 292 
281 275 
ML 
400 390  376  363 351 
342 330 
MH 
485 467  452  441 427 
412 394 
High 
573 555  544  530 513 
493 477 
 
 
 
Recommended operation range 
 
30