All installations and services must be performed by qualified service personnel. 
control, with one of the higher speed blower leads attached to a terminal marked 
“Park”. Be sure to attach any unused blower leads to a terminal marked “Park”. 
Replace the blower door and turn on the power supply. 
 
 
 
F.  FURNACE CHECKOUT PROCEDURE 
 
Before any system of gas piping is finally put into service, it shall be carefully 
tested to assure that it is gas tight as indicated in the Fuel Piping Section of this 
Furnace  Manual. 
 
NOTICE:
 All controls on the unit should be checked for proper functioning prior to 
the qualified service personnel leaving the job site. Specifically the following 
should be checked: 
 
With furnace in normal heating operation, check to make certain blower will start 
and stop automatically under control of  integrated fan control. 
 
1. Check safety limit control as follows: 
a. Shut off incoming power. 
b. Block return air opening or disconnect blower motor leads. 
c. Restore power to furnace. 
d. Set thermostat above room temperature calling for heat. 
e. When temperatures are reached in furnace at limit control setting with 
   blower out of operation, burner  should  shut off. 
f. Shut off electrical power.  
 
 
IMPORTANT:  
Remove blockage or reconnect blower motor and restore power. 
 
2. Make certain thermostat will automatically start and stop furnace. 
 
3. Block the flue pipe outlet gradually with a flat piece of metal, until the pressure 
switch functions shutting off the main burners. IMPORTANT: Remove flue outlet 
blockage when done. 
 
4.  Block the PVC pipe inlet gradually with a flat piece of metal until pressure 
switch functions shutting off the main burners.  IMPORTANT:  Remove air inlet 
blockage when done.  
 
5.  Remove the blower compartment access door with the furnace operating. The 
door interrupt switch is in the 120 volt circuit and will shut down the entire 
system. Replace the blower door and the furnace start-up cycle will begin. 
 
 
 
 
39