R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS
7
68-0105—2
Fig. 9. Positioning the sensing bulb in the immersion well.
WIRING
IMPORTANT
Use Underwriters Laboratories Inc. listed connectors 
when making external circuit connections to the 
orange and white line voltage burner and ignition 
leadwires of the R8182H,J.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
Disconnect power supply before wiring to prevent 
electrical shock or equipment damage.
All wiring must comply with local codes, regulations, and 
ordinances.
IMPORTANT
Terminals on the R8182 are approved for copper 
wire only.
Follow the wiring instructions furnished by the appliance 
manufacturer, if available, or refer to Fig. 11 through 17. For 
wiring multiple zoning systems, refer to Fig. 16 and 17.
The R8182 is equipped with special wiring terminals. Wires 
can be wrapped around the terminal screw or inserted from 
the side.
Method 1
1. Strip 7/16 in. of insulation from the wire end.
2. Wrap the wire 3/4 of the distance around the screw as 
shown in method 1.
3. Using a standard, flat-headed screwdriver, tighten the 
screw until the wipe is snugly in contact with the screw 
and contact plate.
4. Tighten the screw pin an additional one-half turn.
Method 2
1. Strip 5/16 in. of insulation from the wire end.
2. Insert wire beneath the screw as shown in method 2.
3. Using a standard, flat-heat screwdriver, tighten the 
screw until the wire is snugly in contact with the screw 
and contact plate.
4. Tighten the screw an additional one-half turn.
NOTE: Do not use a push-type ratchet screwdriver.
The TRADELINE® R8182D,H can be converted to replace an 
R8182B,C,E,F or a White Rodgers 6C92-2 or 6C92-3. When 
replacing a White Rodgers model, the immersion well must 
also be replaced. Refer to Fig. 10 for Aquastat® limit 
connections necessary for each R8182D conversion. 
To release the wires from the R8182, insert a screwdriver into 
the rectangular hole adjacent to the wire, push inward to 
release the locking-grip on the wire, and pull the wire out of 
the terminal hole. 
To reinsert the wire into a new terminal hole, simply push the 
wire into the new slot.
CONTROLLER
CASE
IMMERSION
WELL CLAMP
ADAPTER
IMMERSION
WELL SPUD
BOILER
OLD IMMERSION
WELL ASSEMBLY
BACK OF
CONTROLLER
CASE
IMMERSION
WELL CLAMP
SCREW
ADAPTER
SENSING 
BULB
HEAT-CONDUCTIVE COMPOUND
SETSCREW
CAPILLARY
TUBE
(C)
IMMERSION
WELL CLAMP
IMMERSION
WELL CLAMP SCREW
SHORT TUBE 
FITS IN CENTRAL
RECESS OF ADAPTER
BEND THE CAPILLARY TUBE TO HOLD THE SENSING BULB IN GOOD 
THERMAL CONTACT WITH THE IMMERSION WELL AT POINTS  (A) AND (B).
ASSURE THAT CAPILLARY TUBE FITS FREELY IN THE ADAPTER SO THE 
TENSION OF THE CAPILLARY TUBE AT POINT (C) HOLDS THE SENSING 
BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINT (D).
M8830
1
1
2
2
(D)
(B)
(A)