Cabinet Series Dehumidifying Dryer 
 
20 
 
E5CK Operating Parameters 
The E5CK has several mode selections. Within each mode are numerous parameters that can be 
set. The setting is different for the temperature control unit and the dew point display.  
Before you can access the several modes of operating parameters, you must change the security 
lock-out of the controller. The factory sets the security level to protect the parameters from being 
accidentally changed. Below is an explanation of the operating modes, how to change out the 
security level and the factory default settings. 
Available E5CK Modes 
Menu Display 
Level 0 Mode 
For normal operation.  Execute AT auto-tuning, change to manual mode. 
Level 1 Mode 
For adjusting primary control parameters. Execute: Set alarm values; set the control period; set 
PID parameters. 
Level 2 Mode 
For adjusting secondary control parameters. The dehumidifying dryer uses E5CK default settings. 
Setup Mode 
For setting the basic specifications. Set parameters for input type, scaling, output assignments and 
direct/reverse operation. 
Expansion Mode 
For setting expanded functions. Set: ST (self-tuning), SP setting limiter. Select: advance PID or 
ON/OFF control. 
Option Mode 
This mode is only accessible when and option board is installed. 
Calibration Mode 
For calibrating communication unit E53-CKF. Not used. 
Manual Mode 
Sets the controller to manual operation mode.  Not used on dehumidifying dryers.