3.4E Installation in an Attic with an  
Existing Forced Air HVAC System 
ALWAYS install a catch pan with a drain and/or float interrupt 
switch for condensate under the Ultra-Aire XT150H in an attic to 
reduce liklihood of water damage. 
Locate a separate return for the Ultra-Aire XT150H in a central 
area of the structure. Duct the supply of the Ultra-Aire XT150H to 
the air supply of the existing HVAC system. Connect an insulated 
duct from outside to the 6" collar of the Ultra-Aire XT150H if you 
wish to provide fresh air ventilation. Adjust damper in the collar 
to provide the desired amount of fresh air. Using a remote control, 
program the unit to bring in the desired amount of fresh air.
3.4F Installation in a Structure with  
Two Forced Air HVAC Systems 
The Ultra-Aire XT150H can be installed into two typical HVAC 
ducting systems. Install a separate return for the Ultra-Aire XT150H 
as directed above. Discharge air from the dehumidifier should be 
split and routed to each supply ducting system. A balancing damper 
and a backdraft damper is required in each duct between the Ultra-
Aire XT150H and the HVAC ducting system. This allows airflow to 
be adjusted and prevents flow of air between the ducting systems. 
Contact the factory for assistance, if necessary.
3.4G Installation in a Structure with No Existing 
Forced Air HVAC System 
When installing the Ultra-Aire XT150H in a structure that does not 
have a forced air HVAC system, a single return for the Ultra-Aire 
XT150H should be installed in central open area of the structure. 
DO NOT locate the return in a bathroom or a kitchen. The supply of 
the Ultra-Aire XT150H should be located in the remote areas of the 
structure (such as bedrooms, den, etc.). By ducting this way, the air 
inside the structure will circulate through the Ultra-Aire XT150H to 
be filtered and dehumidified. Avoid discharging all the air from the 
dehumidifier in one location to prevent heat build up in that area. 4" 
diameter duct is recommended for branches to the bedrooms, 6" 
diameter duct is recommended for branches to larger areas. Refer 
to section 3.4B for branch duct sizing. Connect an insulated duct 
from outside to the 6" collar of the Ultra-Aire XT150H if you wish to 
provide fresh air ventilation. 
3.5 Quiet Installation 
Consider compression vibration and airflow noise during 
installation. Use of flex duct and/or vibration isolation materials 
during mounting and ducting will result in quieter operation.
3.6 Noise Abatement
A length of flexible ducting on all Ultra-Aire XT150H duct 
connections is recommended to reduce noise and vibration 
transmitted to rigid ductwork in the structure. 
4. Controls 
All control panels should be mounted in a central area of the 
structure where it can accurately sense the humidity of the air in 
the living space and be accessed. All controls require field wiring 
from the unit location to the panel mount location. 
To determine how each control operates the Ultra-Aire XT150H, 
it must first be determined which control is being used and 
whether or not the Ultra-Aire XT150H is ducted for fresh air 
ventilation. Refer to appropriate section. 
Humidity/Fan Control Panel (P/N 4024155) (Figure 1, p.7) 
4.1A   
  Humidity/Fan Control Panel WITHOUT Fresh Air   
Ventilation or Damper  
4.1B   
 Humidity/Fan Control Panel WITH Fresh Air   
Ventilation and WITHOUT Damper  
4.1C   
 Humidity/Fan Control Panel WITH Fresh Air  
Ventilation AND Damper  
FOR HVAC INSTALLER ONLY
7
Figure 1:
Humidity/Fan Control Panel
Part No. 4024155
Figure 2: Ventilation Timer  
and Humidity Control Panel
Part No. 4024125
Ultra-Aire XT150H Installer’s & Owner’s Manual