Programming Manual - Basic & Applied Instruction Edition
4 Devices in Detail
4.1 Device Number List
1
Introdu
ction
2
Ov
ervi
ew
3
Instruction 
Li
st
4
D
evices 
in Det
ai
l
5
Specifi
ed the
De
vice
 &
 
C
onst
ant
6
Bef
ore
 
Pr
og
ra
mmi
ng
7
Bas
ic 
Instruction
8
FN
C00-FN
C0
9
Program Fl
ow
9
FNC
10-FN
C19
Mov
e & Com
pare
10
FNC
20-FNC
29
Arith. & Lo
gi
Operati
on
3) FX
3U
/FX
3UC
 PLCs
Device name
Description
Reference
I/O relay
Input relay
X000 to X367
*1
248 points
Device numbers are octal.
The total number of inputs and outputs is 256.
Section 4.2
Output relay
Y000 to Y367
*1
248 points
Auxiliary relay
General type [variable]
M0 to M499
500 points
The setting can be changed between the latched
(battery backed) type and the non-latched type
using parameters.
Section 4.3
Latched (battery backed) 
type [variable]
M500 to M1023
524 points
Latched (battery backed) 
type [fixed]
M1024 to M7679
*2
6656 points
Special type
*3
M8000 to M8511
512 points
Chapter 37
State relay
Initial state (general type 
[variable])
S0 to S9
10 points
The setting can be changed between the latched
(battery backed) type and the non-latched type
using parameters.
Section 4.4
General type [variable]
S10 to S499
490 points
Latched (battery backed) 
type [variable]
S500 to S899
400 points
Annunciator
(latched (battery backed) 
type [variable])
S900 to S999
100 points
Latched (battery backed) 
type [fixed]
S1000 to S4095
3096 points
Timer (on-delay timer)
100 ms
T0 to T191
192 points
0.1 to 3,276.7 sec
Section 4.5
100 ms [for subroutine or 
interrupt routine]
T192 to T199
8 points
0.1 to 3,276.7 sec
10 ms
T200 to T245
46 points
0.01 to 327.67 sec
Retentive type for 1 ms
T246 to T249
4 points
0.001 to 32.767 sec
Retentive type for 100 ms
T250 to T255
6 points
0.1 to 3,276.7 sec
1 ms
T256 to T511
256 points
0.001 to 32.767 sec
Counter
General type up counter
(16 bits) [variable]
C0 to C99
100 points
Counts 0 to 32,767
The setting can be changed between the latched
(battery backed) type and the non-latched type
using parameters.
Section 4.6
Latched (battery backed) 
type up counter
(16 bits) [variable]
C100 to C199
100 points
General type 
bi-directional counter
(32 bits) [variable]
C200 to C219
20 points
−2,147,483,648 to 
+2,147,483,647 counts
The setting can be changed between the latched
(battery backed) type and the non-latched type
using parameters.
Latched (battery backed) 
type 
bi-directional counter
(32 bits) [variable]
C220 to C234
15 points
*1.
Available device numbers vary depending on the PLC. For details, refer to Section 4.2.
*2.
Operation varies when M2800 to M3071 are used in the LDP, LDF, ANDP, ANDF, ORP and ORF instructions.
Refer to Section 7.5 for the details.
*3.
For supported functions, refer to Chapter 37.
For handling of the latched (battery backed) area, refer to Section 2.6.