DO NOT TAMPER WITH WIRES WHEN POWER IS ON!
For alarms that are used as single non-interconnected, stand-alone alarms, do not connect the
yellow wire to anything. Insulate this wire (tape it) in place to make certain the yellow wire cannot
contact any metal parts.
IInterconnected alarms can provide earlier warning of fire than stand-alone alarms, especially
if a fire starts in a remote area of the dwelling. When alarms are interconnected, all alarms
will sound when one alarm first goes into alarm. This alarm may be interconnected with a
total of not more than 24 interconnected devices, i.e., as many as 11 other USI ELECTRIC or
UNIVERSAL model smoke alarms or combination smoke and carbon monoxide (CO and
Natural Gas) alarms;  6 other initiating alarms which may be a combination of USI ELECTRIC
or UNIVERSAL CO Alarms and Heat Alarms; and six other non-initiating devices such as USI
ELECTRIC Relay Modules. Compatible models include: 2995, 5304, MI100, MI106, MDS101,
MDS107, MDS211, 2985, 5303, MI200, MI210 USI-1103, USI-1203, USI-1204, USI-1208 (Part
#USI-1209), USI-1213, USI-3204, USI-7385, USI-7390, USI-7485, USI-7490, USI-7795, USI-2430,
USI-960, SS-785, SS-790, SS-795, SS-2795, SS-2895, CD-9385, CD-9390, CD-9485, CD-9490,
CD-9795, HD-130, RM-100.
Interconnected CO alarms or CO alarm circuit of combination smoke and CO and Natural
Gas alarms will only respond if a CO alarm / event initiates the alarm. All other alarms remain
silent.
Interconnected combination Natural Gas Alarms will only respond if a natural gas event
initiated the alarm. All other alarms remain silent.
Interconnected smoke alarms, heat alarms and relay modules will only respond if a smoke
alarm / event or heat alarm / event initiates the alarm. All CO and Natural Gas alarms remain
silent.
Note that smoke alarms without battery backup will not respond during an AC power failure.
NOTE: Relay Modules/USI-960 will not respond if a CO alarm / event initiates the alarm.
2.
Insert the pin into the hole for the feature you are activating. Refer to the diagram below for
correct placement.
TO DEACTIVATE THE LOCKING FEATURES: To remove the alarm for cleaning or servicing or to
replace the battery, you must first remove the appropriate locking pin, if it has been installed.
1.
Turn off AC power to the circuit.
2.
Use long nose pliers to pull the locking pin out of the hole.
3.
It is now possible to remove the alarm or replace the battery.
WIRING INSTRUCTIONS:
1.
a.
The appropriate power supply is 120 Volt single phase power supplied from a non-switchable
circuit NOT protected by a ground fault circuit interrupter.
b.
Turn off AC power to the circuit before wiring the alarm.
c.
There are three pigtail wires (black, white and yellow) coming from the AC QUICK
CONNECTOR. The proper wire connection is as follows:
WIRES FROM QUICK CONNECTORCONNECT TO
BLACK
"HOT" side of AC line
WHITE
"NEUTRAL" side of AC line
YELLOW
Interconnect wires of other alarms
INSERT ALARM
LOCKING PIN HERE
INSERT BATTERY
LOCKING PIN HERE
Page 8