SECTION 2:  Wiring and installation  
2.1 Field Installation  
Warning
 
Wiring codes and regulations may vary. ATEX requires that supply connection wiring must be rated 
at least 5°C above the maximum ambient temperature of 85°C. Wiring must comply with all applicable regulations 
relating to the installation of electrical equipment in a hazardous area and is the responsibility of the installer. If in 
doubt, consult qualified personnel before wiring the system.  
 
Warning
 
Do not open the transmitter enclosure in a classified area (Do not open when an explosive 
atmosphere may be present).  
Guidelines 
  The safety ground connection of the transmitter is a Green screw found in the enclosure. See Figure 4 for 
Ground screw location. Note: The electronics module has to be removed to access Ground screw. Follow steps 
1-7 under Section ‘1.2.3 Rotating electronics module relative to enclosure and conduit entries’, when 
removing electronics module. 
  If the 4-20mA signal is not used, connect a jumper between the 4 – 20mA terminal and the Common terminal 
to allow analog current levels to be monitored at the Test Jacks on the faceplate. 
  The use of shielded cable is highly recommended for signal, input, output and power wires. Refer to Section 
‘2.1.2 Cable choice and guidelines’ for recommended cable to help eliminate interference caused by 
extraneous electrical or electromagnetic ‘noise’. To meet IEC 61000-1 and IEC 61000-4 EMI requirements, 
follow the recommendations listed under Section ‘2.1.2 Cable choice and guidelines’.  
  In applications where wiring is installed in conduit, conduit must not be used for wiring to any other electrical 
equipment.  
  For effective communication, Net Safety limits sensor separation to 2000 feet using 16AWG wires.  
  Modbus RS-485 connection 2-wire mode, multipoint serial line available. Up to 247 addresses allowed. 
  When developing a RS-485 chain of devices, the last device in the chain requires an end of line termination 
resistor (120 Ohms).  
  Transmitter connector terminals accommodate wire from 14 to 20 AWG wires. 
2.1.1 Seals  
Warning
 
The use of conduit wiring seals is recommended to protect the system against water ingression, and 
equipment should be installed according to local electrical codes. Seals are especially recommended for installations 
that use high-pressure or steam cleaning devices in proximity to the transmitter and/or sensor. The cementing material 
used on the Millennium II sensors is suitable for an operating temperature range of  
(-55°C to +85 °C). 
  Guidelines 
  It is recommended that explosion-proof drains and conduit breathers be used. In some applications, alternate 
changes in temperature and barometric pressure can cause ‘breathing’ which allows moist air to enter and 
circulate inside the conduit. Joints in the conduit system are seldom tight enough to prevent this ‘breathing’.  
  Threaded connections on the enclosure between the enclosure and conduit pipe need to be sealed with thread 
tape, such as Teflon tape, or something similar.  
  Hydrophobic filters (IPF-001) may be used to protect sensors from water.