2.1.6 Remote Reset 
If the alarm relays are configured for latching operation it may be desirable to reset latched alarms from a remote 
location. In this case a normally open, momentary push-button switch may be connected across terminals RST and 
COM. 
 
Figure 10: Remote Reset wiring 
 
 
 
 
                      
                              
                                                            
 
 
2.1.7 Sensor Separation/ Remote mounting of sensor 
When necessary to mount sensor remotely (separated from transmitter) by way of junction box and conduit, it is 
important that the installer follow the necessary requirements and guidelines relating to sensor separation and cable 
selection. See Figure 11 for typical remote mounting of sensor. Also refer Section ‘2.1.2 Cable choice and guidelines’ 
for cable selection and wiring guidelines.  
 When sensors are being mounted remotely, consult the multi-purpose junction box manual (MAN-0081) for wiring 
instructions. Always ensure that the transmitter is supplying 10.5 - 32Vdc across the sensor power terminals (Vdc + 
and Com (-) ) of Net Safety junction box (JB-MPD-A/S). 
 
The maximum distance between the sensor and transmitter is limited by the resistance of the connecting wiring, which 
is a function of the gauge of the wire being used. For effective communication, Net Safety limits the separation 
distance between sensor and transmitter to 2000ft using 16 AWG wire. See Appendix B for information on wire gauge 
and resistance.  
 
Figure 11: Sensor separation/remote mounting of sensor