SECTION 3:  Transmitter and faceplate description 
3.1 Transmitter Power Up   
After power is applied to the transmitter, a warm-up routine will begin, the duration of which depends on the sensor 
type. The display will indicate the sensor warming up and the Status LED will flash Slow Red and current output will 
be 3.0mA.  After the warm-up period, the transmitter will enter normal operation and the screen will display:  
“Channel 1   00 %LEL (or PPM), Channel 2   00 %LEL (or PPM).”  For dual channel models either channel can 
be disabled if not in use. If a channel is disabled, the screen will display: “Disabled” for that particular channel. The 
enabled channel analog output will be to 4.0 mA during normal operation. 
 
 
Figure 14: Faceplate description 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Note: A slow flash is defined as the Status LED being ‘ON’ for 50 milli-seconds and ‘OFF’ for 1 second, while a fast 
flash is the LED being ‘ON’ for 250 milli-seconds and ‘OFF’ for 250 milli-seconds and a very fast flash is the LED 
‘ON’ for 50 milli-seconds and ‘OFF’ for 50 milli-seconds. 
 
3.2 Display 
The Millennium II is equipped with an Organic LED (O LED) display. It allows the user to see the concentration of 
gas present for each individual channel and the various options offered. The display has a wide temperature rating and 
will operate well in lowly lit conditions. In order to extend the life of the display, a screen saver is enabled if the menu 
is not in use. To exit the screen saver mode, move the magnet close to any of the three Reed switch locations (8 o’ 
clock, 6 o’ clock
 or 4 o’ clock position)See Figure 14 and Figure 15.