Table 6: Current output and meaning (cont’d)      
Reg. Value 
Current Output 
(mA) 
Status LED 
Meaning 
Red 
Green 
15 
2.5 
Fast Flash 
 
Sensor Element Failure 
16 
20.0 
Solid 
 
The concentration value is greater than the 
allowed range; the sensor is displaying its 
maximum concentration value.  
17 
2.5 
Fast Flash 
 
FAULT DETECTED: Sensor baseline has 
drifted into a “Negative Gas Concentration” 
region (Zero Drift) and requires re-calibration. 
18 
4-20 
Fast Flash 
 
 Sensor is nearing end of life. Replace at next 
calibration. 
20 
2.5 
Fast Flash 
 
FAULT DETECTED: A critical memory fault 
has occurred. 
21 
2.5 
Fast Flash 
 
FAULT DETECTED: A fault has occurred in 
the sensor’s onboard power supply. 
 
Note:
 A slow flash is defined as the Status LED being ‘ON’ for 50 milli-seconds and ‘OFF’ for 1 second, while a fast 
flash is the LED being ‘ON’ for 250 milli-seconds and ‘OFF’ for 250 milli-seconds and a very fast flash is the LED 
‘ON’ for 50 milli-seconds and ‘OFF’ for 50 milli-seconds. 
 
5.4 RS-485 Modbus RTU  
RS-485 Modbus RTU protocol is used. Tables 7 and 8 on the following pages give the detailed MODBUS registers 
and the bit values for the transmitter register. 
 
The Millennium II Transmitter utilizes 2- wire Modbus RS-485 multi serial mode. This Modbus solution implements a 
2-wire electrical interface in accordance with the EIA/TIA-485 standards. For this MODBUS configuration, it is 
important that a third wire be used for connecting all the ‘Common’ (COM) in the chain. Also a 120 Ohm line 
termination is required for the last device in the line. See Figure 19. The Instrument Engineer is responsible for 
calculating line length and adhering to MODBUS protocols.  
 
Figure 19: Two (2)-Wire Modbus configuration