MAN-0076 Rev 05 Millennium II 
December 07, 2012 
Net Safety Monitoring Inc 
 
INTRODUCTION 
Building on the outstanding legacy of the Millennium Series, Net Safety’s latest innovation in this line of continuously 
evolving  industrial  transmitters  and  sensors,  the  Millennium  II,  pushes  the  boundaries  of  what  you  can  expect  from 
your detection system. Combined with state of the art “Smart” sensors, users will receive a detection system which is 
both versatile and reliable for fast, accurate and continuous monitoring of gases in extreme environments.  
 
THE PRODUCT 
TRANSMITTER/CONTROLLER 
A Millennium II gas detection system is composed of a field mounted transmitter\controller and Millennium II 
series sensors which may be integrally mounted to the controller or remotely mounted as far as 2000 feet away. 
 
The transmitter is certified for use in hazardous locations and is available as a single or dual sensor system. All 
operator controls including configuration and calibration can be accessed without opening the enclosure by using other 
communication devices and the attached magnet to actuate reed switches. If the area is non-hazardous and the 
enclosure (housing) is open then the operator may choose to use push-button switches and analog output test jacks on 
the face of the electronics module. Available outputs are: conventional 0.0 to 20mA analog, Analog/HART, 
electromechanical relays, solid-state relays or Modbus RTU digital. 
 
A dual channel transmitter is available with "peak picking" functionality where there is only one analog output and this 
analog output follows the signal from the sensor that is responding to the highest gas concentration. This is useful in 
conserving analog input capacity on connected user equipment
 
THE MANUAL 
This manual has been designed to guide users through each procedure, ensuring that transmitters and sensors are 
configured, operated and maintained properly. Guidelines and warnings are included to ensure safe and proper 
functioning of the equipment. The manual gives the overall operational and functional features of transmitters 
with sensors and may not have sensor specific information
.  Refer to sensor manuals for information specific to 
each sensor including detailed calibration instructions
. If you encounter any problems, see the troubleshooting 
section of this manual or contact factory.  
Special conditions of use: 
 
M2a-b-c, Millennium II Transmitter with enclosure: 
  
 
1.  In order to maintain the performance of the system, the sensor to which this instrument is connected 
shall also comply with the requirements of EN 61779-1 and EN 61779-4 
 
 
TX-M2a-b, Millennium II Transmitter Electronics module only (w/o enclosure): 
 
1.  If the Millennium II Transmitter is installed as Category 3 equipment, then it shall be installed in an 
Enclosure which maintains an ingress protection rating of IP54 and meets the enclosure requirements 
of EN 60079-0. 
2.  In order to maintain the performance of the system, the sensor to which the instrument is connected  
shall also comply with requirements of EN 61779-1 and EN 61779-4