Macurco DVP-120 ユーザーズマニュアル

ページ / 37
Revision 0.07 
13 
2.6  Horn & Strobe Connection 
The external horn and strobe connections are available at the modular connector J5 (see Figure 2-3 for details). 
J5 as a 4-position connector, similar to the sensor interface connectors. 
 
Insert this face of connector
into mating connector on
control circuit board.
Strobe -
Horn -
Horn +
Strobe +
1
4
 
Figure 2-3 Horn & Strobe Connector 
 
To install the wiring for the horn or strobe, disconnect the connector  from  the header on the PCB. Strip the 
insulation of each wire back  approximately 0.25 in. (6 mm), insert the bare wire into the terminal and tighten 
the screw clamp. Ensure that the wire cannot easily be pulled from the connector. 
 
When all wires are connected, seat the modular connector into the PCB header; ensure that the latch engages. 
 
Refer to Table 2-6 for signals, connector and terminal assignment for the horn and strobe. 
 
Signal Name 
Connector-Pin 
Number 
Signal Name 
Connector-Pin 
Number 
Horn + 
J5-1 
Strobe + 
J5-3 
Horn - 
J5-2 
Strobe - 
J5-4 
Table 2-6 Horn & Strobe signals and Connector Assignments 
Refer to Table 2-7 for recommended wire gauge vs. run length for the horn & strobe functions (maximum 2.5 
volt drop in the wire). 
 
Maximum Run Length (ft.) 
Wire gauge 
(feet) 
(meters) 
24 
200 
61 
22 
340 
103 
20 
480 
147 
18 
850 
215 
Table 2-7 Wire gauge for Horn & Strobe functions