 INSTALLATION 
 
 
This appliance is designed to be vented with a 4” x 6 5/8” direct-vent pipe. Each direct-vent appliance must use its own separate vent 
system
 
 
PAGE 7 
VERTICAL TERMINATION 
WITH NO OFFSETS 
Min. Vertical Pipe Length: 5 feet 
 
Max. Vertical Pipe Length: 25 
feet 
 
 
 
 
VERTICAL TERMINATION  
WITH 2 OFFSETS 
Min. Vertical Pipe From Appliance to first 
offset: 2 feet (*see note). 
 
Min. Total Vertical Pipe Length: 5 feet 
 
Max. Total Vertical Pipe Length: 25 feet 
 
 
 
 
HORIZONTAL TERMINATION  
WITH 1 OFFSET 
Min. Vertical Pipe From Appliance to offset: 
2 feet (*see note). 
 
Max. Vertical Pipe Length: 25 feet 
 
 
 
 
 
Maximum total offsets allowed: Not to exceed 180 degrees. 
Maximum allowable horizontal pipe run is 16 feet. 
With 2 feet of vertical pipe installed from the appliance (* see note), a 2 foot maximum horizontal run allowed. For installations with 
more than 2 feet of vertical pipe, calculate allowable horizontal run as indicated in applicable illustration above. 
See page 10 for Vent Termination Requirements. 
Also see pipe manufacturers instructions for additional vent installation requirements. 
 
Horizontal vent clearances: 3“ minimum top 1“ minimum on bottom and sidewalls. 
 
Vertical vent clearances: 1” minimum. 
Install vent support brackets every 4 feet of vertical pipe unless otherwise specified by vent manufacturer. 
Note: If using Propane Gas (LP), it may be necessary to install (as a minimum) 3 feet of vertical pipe from the appliance prior to an 
offset to ensure optimum product performance. This may be necessary due to variations in vent configuration and other numerous 
factors which affect exhaust flow and air delivery such as BTU value, ambient temperature, wind conditions, altitude, etc.
 
For every 1 feet of 
vertical pipe (from 
unit to first offset), 2 
feet of horizontal 
run is allowed (not 
to exceed 16 ft. 
Example – with a 6’ ver-
tical pipe off unit, 12’ of 
horizontal run is allowed.
At 2’ Min. Vertical, 2’ Max. 
Horizontal is allowed. 
Horizontal 
runs require 
¼” rise per 
foot. 
* 2 Feet Min.
5 Feet
Min.
 
25 
Feet
Max.
For every 1 feet of vertical 
pipe (from unit to first offset), 
2 feet of horizontal run is 
allowed (not to exceed 16 ft. 
Example – with a 8’ ver-
tical pipe off unit, 16’ of 
horizontal run is allowed.
* 2 Feet Min.
5 Feet 
Min. 
 
25 Feet 
Max.
 
25 
Feet
Max.
Horizontal runs 
require ¼” rise 
per foot. 
16 Feet Max.
Wall 
Penetration  
Detail