FLOOR PROTECTION
INSTALLING FIREPLACE ON COMBUSTIBLE FLOOR
If fireplace is installed on a combustible floor, protect the floor area either side of the fireplace opening and in the front 
with an insulating non-combustible hearth extension. (16" [400 unit] or 20" [500 unit] minimum in front of fireplace and 
8" minimum on both sides. See Figures 6 through 12.
Fireplace 
Platform May Extend Under Hearth 
Extension if Desired 
Platform
(If Necessary)  
Metal Safety Strip Must Be 
Use if Unit Is Placed on 
Combustible Floor 
Metal Safety Strip 
Must Be Use if 
Unit Is Placed on 
Combustible Floor 
Figure 6 - Installing Floor 
Protection (Circulating Model) 
Figure 6 - Installing Floor Protection (Radiant Model) 
Fireplace 
  Hearth Extension Clearances & Width 
   
400 Unit 
500 Unit
  On Both Sides 
8" Min. 
8" Min.
  Front of Fireplace  16" Min. 
20" Min.
  Extension Width 
52"  
66" 
Note:  Do  not  block  the  side  air 
vents or air inlet louvers on 
the lower front of the fireplace 
with hearth extension. 
Air  vents  and  air  inlet  louvers  allow 
necessary  cooling  air  around  the  fire-
place. Determine the finished height of 
the hearth extension to be used. Raise 
the fireplace on a platform, if necessary, 
to prevent blocking of air openings and 
lower louvered panel.
Note:  No platform is needed if 
hearth extension does 
not exceed 1" thick for 
circulating units or 6½" for 
radiant units. 
Air Vents — DO NOT BLOCK