TRIM AND MANTEL INSTALLATION FOR WOOD BURNING FIREPLACES 
•  The fireplace face may be left exposed or trimmed. If trim is installed, fasten it securely to face of fireplace. Seal any 
cracks between trim material and face of fireplace. Cracks can cause a fire and prevent fireplace from working prop-
erly.
•  Place wall ties in mortar joints of masonry trim. Fasten wall ties to face of fireplace with sheet metal screws. 
•  Use only non-combustible materials below top of spacers. 
Seal  any  space  between  face  of 
fireplace and non-combustible facing 
material. Failure to seal this crack is a 
possible fire hazard and will void the 
warranty. 
W
ARNING
Do not cover or restrict 
side vent areas with 
surround or trim materials 
W
ARNING
LOCATING FRONT AND SIDE CLEARANCES 
To find front clearances, extend a line from back corner of 
unit to 4" in front of fireplace face and 1" outside screened 
opening. Combustible materials may be placed within shaded 
areas. Note: Do not let combustible materials overlap 
black painted surface more than 
1
/
8
". 
See Figure 41.
Trim may butt against side walls of fireplace. The other 3 walls 
must have ¾" clearances. 
Figure 40 - Spacer Location 
Figure 41 - Front and Side Clearances 
Figure 42 - Locating Mantel 
LOCATING MANTEL 
Maximum depth of mantel is 12"
A =  6½"  -  Minimum from top of fireplace opening to bottom 
of any combustible trim material sticking out no 
more than 1½" beyond face of fireplace 
B =  12" -  Minimum from top of fireplace opening to bottom 
of combustible trim material sticking out more 
than 1½" from top of fireplace opening
Top of 
Fireplace 
Opening 
Combustible 
Wallboard  
Non-Combustible 
Trim 
Area to Be 
Sealed 
Combustible 
Mantel
 Non-
Combustible 
Surround Trim 
¾" 
Separation 
0" Clearance 
to Front Side 
Walls 
4" Reference 
Extended Line 
1" Reference 
Combustible 
Material 
within Shaded 
Area 
Combustible 
Wallboard