Regency P36-LP4 ユーザーズマニュアル

ページ / 8
6-7/8"
(173mm) dia.
Flue pipe
4" (102mm)
dia. flue pipe
Termination Cap
Part #946-523/P
AstroCap
spring
spacer
Wall Thimble (2 pc)
FPI Direct  Vent System (Flex)
Horizontal Terminations Only
These venting systems, in combination with the P36 / P36D Direct Vent 
Gas Fireplace, have been tested and listed as a direct vent heater system 
by Warnock Hersey. The location of the termination cap must conform 
to the requirements in the Vent Terminal Locations diagram.
FPI Direct Vent (Flex) System Termination Kits include all the parts 
needed to install the P36 / P36D using a fl exible vent.
FPI Kit # 
Length 
Contains:
#946-515
4 Feet
1) 
6-5/8” fl exible liner (Kit length)
2) 
4” fl exible liner (Kit length)
3) spring 
spacers 
(3)
4) thimble 
(2)
5) 
AstroCap termination cap (1)
6) screws 
(12)
7) 
tube of Mill Pac (1)
8) plated 
screws 
(8)
9) 
S.S. screws #8 x 1-1/2” drill point, (4)
#946-516
10 Feet
Notes: 
1) 
Liner sections should be continuous without any joints or seams.
2) 
Only Flex pipe purchased from Regency may be used for Flex 
installations.
3) 
Horizontal sections must be supported every 3 feet.
Alternate Horizontal 
Termination Caps
Alternate:
Horizontal
Riser Vent
Terminal
Part# 640-530/P
Snorkel Terminations
Snorkel Terminations:
For installations requiring a vertical rise on the exterior of the building, 
14-inch and 36-inch tall Snorkel Terminations and the Riser Vent are 
available. Follow the same installation procedures as used for standard 
Horizontal Termination. NEVER install the snorkel upside down.
Below Grade Snorkel Installation (Dura-Vent Only)
If the Snorkel Termination must be installed below grade, i.e. basement 
application, proper drainage must be provided to prevent water from 
entering the Snorkel Termination. Refer to Rigid Pipe Installation 
instructions for details. Do not attempt to enclose the Snorkel within the 
wall, or any other type of enclosure.
P36 - P36D Gas Fireplace
If required by the external termination location the listed 
alternate termination caps may be used.  (Refer to Page 11)
37
June 2007 Regency Product Specifi cations Book
Gas Fireplaces