Enviro 50-029 ユーザーズマニュアル

ページ / 33
Initial Installation
24" (610mm)
Maximum
Horizontal
24" (610mm)
Minimum
Vertical
Inside
Finished
Collar
Wall
Thimble
Horizontal
Vent
Termination
Exterior
Wall Surface
Insulation
Interior Wall
Surface
If installed on a
carpeted surface
a hearth is required
Interior
Wall Surface
2.5"
(64mm)
Inside
Finished
Collar
Horizontal
Vent Section
Exterior
Wall Surface
Horizontal
Vent
Termination
Wall
Thimble
Insulation
If installed on a
carpeted surface
a hearth is required
NOTES:  
(1) 
The horizontal run of vent pipe must be 
level and should have a 1⁄4 inch rise 
for  every  one  foot  of  run  towards 
the  termination.  Never  allow  the 
vent to run downward. This could cause 
high  temperature  and  may  present  the 
possibility of a fire.
(2)  The  location  of  the  horizontal  vent 
termination on the exterior wall must not 
be easily blocked or obstructed. Refer to 
“Initial  Installation  -  Vent  Termination 
Restrictions” section.
(3)  When  installing  a  vent  pipe  in  a  chase 
the minimum clearance to combustibles 
is 2” (51 mm).
NOTE:  Vent  pipe  must  not  be  longer 
than  18”  (457  mm)  maximum  when 
installing straight through exterior wall.
Maintain  manufacturer’s  clearances  to 
combustibles with venting.
Vent may extend between 6 inches (152 
mm) and 18 inches (457 mm) maximum 
straight out.
When installing this unit in a corner the 
maximum distance after 45˚ elbow is 9 
inches (228 mm).
If between 9 inches (229 mm) and 24 
inches (610 mm), a 14 inches (356 mm) 
snorkel must be used.
16
Figure 17: Straight Through Wall Installation.
Figure 18: Up Then Through Wall Installation.