TABLE 1 – first stage pipe sizing
10 PSIG Inlet with a 1 PSIG Pressure Drop
Maximum capacity of pipe or tubing, in thousands of BTU/hr. of L.P. Gas
Size of Pipe
              LENGTH OF PIPE OR TUBING, FEET*
Or Copper
Tubing, Inches
1 0
2 0
3 0
4 0
5 0
6 0
7 0
8 0
9 0
1 0 0
3/8
558
3 8 3
3 0 9
2 6 5
2 3 5
2 13
1 96
1 8 2
1 7 1
1 61
Copper
½
1387
8 7 0
70 0
59 9
5 3 1
4 81
4 4 3
4 1 2
3 86
3 6 5
Tubing
5/8
2360
1622
1303
1115
9 8 8
8 96
8 2 4
7 6 7
71 9
6 7 9
(O.D.)
¾
3993
2475
2205
1887
1672
1515
1394
1297
1217
1149
½
3339
2295
1843
1577
1398
1267
1165
1084
1017
9 6 1
Pipe
¾
6982
4799
3854
3298
2923
2649
2437
2267
2127
2009
Size
1
13153
9040
7259
6213
5507
4989
4590
4270
4007
3785
1-1/4
27004
18560
14904
12756
11306
10244
9424
8767
8226
7770
1-1/2
40461
27809
22331
19113
16939
15348
14120
13136
12325
11642
2
77924
53556
43008
36809
32623
29559
27194
25299
23737
22422
125
1 5 0
1 7 5
2 0 0
2 2 5
2 50
2 75
3 0 0
3 5 0
4 00
3/8
142
1 3 0
1 1 8
1 1 1
1 0 4
9 0
8 9
8 9
8 2
7 6
Copper
½
323
2 9 3
2 6 9
2 5 1
235
222
211
201
185
172
Tubing
5/8
601
5 4 6
5 0 2
4 6 7
438
414
393
375
345
321
(O.D.)
¾
1018
9 2 3
84 3
79 0
7 4 0
7 00
6 6 4
6 3 4
5 84
5 4 3
½
852
7 7 2
7 1 0
6 6 0
6 1 9
5 85
5 56
5 3 0
4 8 8
4 54
Pipe
¾
1780
1613
1484
1381
1296
1224
1162
1109
1020
9 4 9
Size
1
3354
3039
2796
2601
2441
2305
2190
2089
1922
1788
1-1/4
6887
6240
5741
5340
5011
4733
4495
4289
3945
3670
1-1/2
10318
9349
8601
8002
7508
7092
6735
6426
5911
5499
2
19871
18005
16564
15410
14459
13658
12971
12375
11385
10591
*Total length of piping from outlet of first stage regulator to inlet of second stage regulator (or to inlet of second stage regulator furthest
away).
Notes:
1)  To allow 2 PSIG pressure drop, multiply total gas demand by .707, and use capacities from table.
2 )
For different first stage pressures, multiply total gas demand by the following factors, and use capacities from table.
First State Pressure PSIG         Multiply by
2 0
.844
2 1
.912
Data Calculated per NFPA #54 & 58.
TABLE 4 – Second, Single, or Integral Twin Stage Pipe Sizing
11 Inches Water Column Inlet with a ½ Inch Water Column Drop
Maximum capacity of pipe or tubing in thousands of BTU/hr of LP-Gas
Size of Pipe
LENGTH OF PIPE OR TUBING, FEET*
Or Copper
Tubing, Inches
1 0
2 0
3 0
4 0
5 0
6 0
7 0
8 0
9 0
10 0
3/8
4 9
3 4
2 7
2 3
2 0
1 9
Copper
1/2
110
7 6
6 1
5 2
4 6
4 2
3 8
3 6
3 3
3 2
Tubing
5/8
206
1 4 1
11 4
9 7
8 6
7 8
7 1
6 7
6 2
5 9
(O.D.)
3/4
348
23 9
1 92
1 6 4
1 4 6
1 32
1 2 0
1 1 3
1 05
1 0 0
7/8
536
3 6 8
29 6
25 3
2 2 4
2 03
1 8 5
1 7 4
1 61
1 5 4
1/2
291
2 0 0
16 1
13 7
1 2 2
1 10
1 0 2
9 4
8 7
8 4
Pipe
3/4
608
4 1 8
3 3 6
28 7
255
231
212
198
185
175
Size
1
1146
7 8 8
6 3 2
5 4 1
4 8 0
4 3 5
4 0 0
3 72
3 4 9
3 3 0
1-1/4
2353
1617
1299
1111
9 8 5
8 92
8 2 1
76 4
7 1 7
6 7 7
1-1/2
3525
2423
1946
1665
1476
1337
1230
1144
1074
1014
2
6789
4666
3747
3207
2842
2575
2369
2204
2068
1954
125
1 5 0
17 5
20 0
2 2 5
2 50
2 7 5
3 0 0
3 50
4 0 0
3/8
Copper
1/2
Tubing
5/8
(O.D.)
3/4
7/8
1/2
7 4
6 7
6 2
5 8
5 4
5 1
4 8
4 6
4 3
4 0
Pipe
3/4
155
1 4 1
1 2 9
12 0
113
107
101
9 7
8 9
8 3
Size
1
292
2 6 5
24 4
22 7
213
201
191
182
167
156
1-1/4
600
5 4 4
5 0 0
4 6 5
437
412
392
374
344
320
1-1/2
899
8 1 5
7 4 9
6 9 7
654
618
587
560
515
479
2
1731
1569
1443
1343
1260
1190
1130
1078
9 92
9 2 3
*Total length of piping from outlet of regulator to appliance furthest away.
Data Calculated per NFPA #54 & 58.
Page 8
PROPANE GAS
PROPANE GAS