2.1.1 Hearth Requirements 
 
If the non-combustible hearth is flush with the floor, then the hearth must be 16”/406mm 
(18”/450mm  in  Canada)  in  front  of  the  fan  housing  (see  Figure  2.1.2).    If  the  non-
combustible hearth is a minimum of 4” (102mm) above the floor, then the hearth can be 6” 
(152mm) out from the fan housing with  a 10” (254mm) floor protection (sparks) extended 
beyond the hearth (see Figure 2.1.1).  The non-combustible hearth must be a minimum of 8” 
(203mm) on each side of the unit (Canada & USA). 
 
Convert specification to R-value: 
 
k-factor is given with a required thickness (T) in inches: R=1/k x T 
 
C-factor is given: R=1/C 
 
Example: 
If the floor protector is 4” brick with a C-factor of 1.25 over 1/8” mineral board with a k 
factor of 0.29 the total R-value of the system is: 
 
4” brick C=1.25, R=1/1.25=0.8 
 
1/8” mineral board K=0.29, R=1/0.29 x 0.125=0.431 
 
Total R = Rbrick + Rmineral = 0.8 + 0.431 = 1.231 
 
Total R is greater than 1.0, the system is acceptable. 
 
 
 
   
   
 
Figure 2.1.1   
 
 
 
 
 
 
 
       Figure 2.1.2 
 
2.2 Suitable Fireplace Dimensions 
 
Escape 1400-I 
Measurement for :  
 
Minimum 
Opening Height (F) 
21½” (546 mm) 
Opening Width (G) 
29” (737 mm) 
Opening Depth (H) 
14” (356 mm) 
Table 2.2