Fireplace inSTallaTion
SELECTING LOCATION
To determine safest and most efficient location 
for fireplace, you must take into consideration 
the following guidelines:
1.  Location must allow for proper clearances 
(see Figures 1 and 2).
2.  Consider  a  location  where  fireplace  will 
not be affected by drafts, air conditioning 
ducts, windows or doors.
3.  A location that avoids cutting of joists or 
roof rafters will make installation easier.
4.  An  outside  air  kit  is  available  with  this 
fireplace (see Optional Outside Air Kit on 
page 7).
MINIMUM CLEARANCE TO 
COMBUSTIBLES
Back and sides of fireplace   3/4" minimum*
Floor** 
0" minimum
Perpendicular wall to opening  14" minimum
Top spacers 
0" minimum
Mantel clearances 
see Mantels, page 6 
Chimney outer pipe surface 
1" minimum
* Not required at nailing flanges
** See step 2 of Framing
 WARNING: Do not pack re-
quired air spaces with insulation 
or other materials.
Minimum/Maximum Chimney Height
Minimum height of chimney, measured from 
base of fireplace to flue gas outlet of termina-
tion, is 11.5 feet for straight flue or a flue with 
one elbow set. Maximum distance between 
elbows is 2 feet. For systems with two elbow 
sets,  minimum  height  is  22  feet.  Maximum 
height of any system is 50 feet. This measure-
ment includes fireplace, chimney sections and 
height of termination assembly at level of flue 
gas outlet (see Figure 18, page 11).
FRAMING
1.  Frame opening for fireplace using dimen-
sions shown in Figures 1 and 2.
2.  If  fireplace  is  to  be  installed  directly  on 
carpeting, tile (other than ceramic) or any 
combustible  material  other  than  wood 
flooring, fireplace must be installed upon 
a metal or wood panel extending full width 
and depth of fireplace.
3.  Set fireplace directly in front of this open-
ing and slide unit back until nailing flanges 
touch side framing.
4.  Check  level  of  fireplace  and  shim  with 
sheet metal if necessary.
5.  Before  securing  fireplace  to  prepared 
framing, ember protector must be placed 
between hearth extension (not included) 
and under bottom front edge of fireplace 
to protect against glowing embers falling 
through. If fireplace is to be installed on 
a raised platform, a Z-type ember protec-
tor  (not  included)  must  be  fabricated  to 
fit your required platform height. Ember 
protector should extend under fireplace a 
minimum of 1 
1
/
2
". Ember protector should 
be made of galvanized sheet metal (28 
gauge minimum) to prevent corrosion.
6.  Using screws or nails, secure fireplace to 
framing through flanges located on sides 
of fireplace.
22"
37.625"
44.25"
Figure 1 - Framing Dimensions
52 
1
/
2
"
15 
7
/
8
"
22 
1
/
2
"
72 
7
/
8
"
Maintain 3/4"
Clearance at
Sides and
Back of
Fireplace
3/4" Clearance Not 
Required at Nailing Flanges  
Figure 2 - Corner Installation