Sterling GG-105 ユーザーズマニュアル

ページ / 44
4
Table 1 - Performance and Dimensional Data - Tubular 30 thru 120 Propeller Unit Heater
 
Unit 
Size 
30 45 60 75 90 105 
120
 PERFORMANCE DATA†
 
Input 
BTU/Hr. 
30,000 45,000 60,000 75,000 90,000 105,000 
120,000
                  (kW) 
(8.8) 
(13.2) 
(17.6) 
(22.0) 
(26.4) 
(30.8) 
(34.2)
 
Output 
BTU/Hr. 
24,300 36,450 48,600 60,750 72,900 85,050 97,200
                     (kW) 
(7.1) 
(10.7) 
(14.2) 
(17.8) 
(21.4) 
(24.9) 
(28.5)
 
Thermal 
Effi 
ciency 
(%) 
81 81 81 81 81 81 81
  Free Air Delivery - CFM 
370 
550 
740 
920 
1,100 
1,300 
1,475
                         (cu. m/s) 
(.175) 
(.260) 
(.349) 
(.434) 
(.519) 
(.614) 
(.696)
 
Air 
Temperature 
Rise 
Deg. 
60 60 60 60 60 60 60
                                     (Deg. C) 
(15) 
(15) 
(15) 
(15) 
(15) 
(15) 
(15)
 
Full 
Load 
Amps 
at 
120V 
 
3.0 3.0 3.7 4.1 6.4 6.4 6.4
  Maximum 
Circuit 
Ampacity 
3.5 3.5 4.4 4.8 7.5 7.5 7.5
 MOTOR DATA: Motor HP 
1/20 
1/20 1/12 1/12 1/10 1/10 1/10
 
 
Motor 
 
(kW) 
(0.04) (0.04) (0.06) (0.06) (0.075) 
(0.075) 
(0.075)
 
 
Motor 
Type 
SP SP SP SP SP SP SP
 
 
R.P.M. 
1650 1650 1050 1050 1050 1050 1050
 
 
Motor 
Amps 
115V 
1.9 1.9 2.6 2.6 4.2 4.2 4.2
  DIMENSIONAL DATA  - inches (mm)
 
“A” 
Jacket 
Height 
12-3/8 12-3/8 15-7/8 15-7/8 22-5/8 22-5/8 22-5/8
 
 
(314) (314) (403) (403) (574) (574) (574)
  “B” Overall Height 
13-1/4 
13-1/4 
16-13/16 
16-13/16 
23-9/16 
23-9/16 
23-9/16
 
 
(337) (337) (427) (427) (598) (598) (598)
 
“C” 
Overall 
Depth 
25-7/8 25-7/8 26-3/16 
26-3/16 26-3/8 26-3/8 26-3/8
 
 
(632) (632) (665) (665) (670) (670) (670)
  “D1” Center Line Height of Flue* 
8-1/2 
8-1/2 
10-3/8 
10-3/8 
13-5/8 
13-5/8 
13-5/8
 
 
(216) (216) (263) (263) (346) (346) (346)
  “D2” Center Line Height of Air Intake 
8-1/2 
8-1/2 
8-5/8 
8-5/8 
8-5/8
 
 
(216) (216) (203) (203) (219) (219) (219)
 
“E” 
Fan 
Diameter 
10 10 14 14 16 16 16
 
 
(254) (254) (356) (356) (406) (406) (406)
  “F” Discharge Opening Height 
10-13/16 
10-13/16 
14-7/16 
14-7/16 
21-3/16 
21-3/16 
21-3/16
 
 
(275) (275) (367) (367) (538) (538) (538)
 
“G” 
Vent 
Connection 
Diameter 
4 4 4 4 4 4 4
 
 
(102) (102) (102) (102) (102) (102) (102)
  “H1” Center Line of Flue Connection From Side 
7-1/4 
7-1/4 
7-1/4 
7-1/4 
7-3/4 
7-3/4 
7-3/4
 
 
(184) (184) (184) (184) (197) (197) (197)
  “H2” Center Line of Air Intake From Side 
2-3/4 
2-3/4 
2-3/4 
2-3/4 
3-1/2 
3-1/2 
3-1/2
 
 
(70) (70) (70) (70) (89) (89) (89)
  Vent Size Requirements - Standard Combustion 
       Category I Horizontal** 
5
 
 
(102) (102) (102) (127) (127) (127) (127)
       Category III Horizontal 
4
 
 
(102) (102) (102) (102) (102) (102) (102)
       Category I & III Vertical 
4
 
 
(102) (102) (102) (102) (102) (102) (102)
  Vent Size Requirements - Separated Combustion
       Exhaust Diameter** 
5
 
 
(102) (102) (102) (102) (127) (127) (127)
       Intake Air Diameter 
5
 
 
(102) (102) (102) (102) (127) (127) (127)
 
Unit 
Weight 
lbs. 
57 60 75 87 96 103 
112
                      (kgs) 
(27) 
(29) 
(34) 
(37) 
(45) 
(48) 
(49)
 
Shipping 
Weight 
lbs. 
67 70 90 96 109 
143 
152 
                              (kgs) 
(32) 
(33) 
(41) 
(44) 
(51) 
(66) 
(67)
*  For all installations, the fl ue collar is included with the unit and should be fi eld installed per the instructions included with the unit.
** 4-5" reducer supplied where required.
†  Ratings shown are for unit installations at elevations between 0 and 2,000 ft (0 to 610m). For unit installations in U.S.A. above 2,000 ft. (610m), the unit input must be derated 4% for each 1,000 ft. (305m) above sea 
level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54), (also refer to Table 6).