Energy Tech Laboratories 5357 ユーザーズマニュアル

ページ / 20
Fault Code
Meaning of Code
OFF
The desired programmed temperature point is lower than 60°F (15°C).
LP & LP3
Shortage of refrigerant gas in the unit or faulty low pressure control. The unit will show
(LP3) after LP faults and shuts down the unit and pool pump for protection. If this
occurs, you should call for service.
HP & HP6
Low water flow in the unit or faulty high pressure control. Check water flow/backwash. The
unit will show (HP6) after 6 HP faults. This will stop the unit for protection.
FLo & FL3
Possible causes:
• The filter is in backwash position.
• The filter pump is stopped.
• The filter is dirty.
• Shortage of water to pool pump.
• FIL parameter must be set to activate pool pump.
• Water pressure switch must be adjusted or it is broken.
• The unit is in the protection mode and will show (FL3), press any key to restart the unit.
FL3 code will stop the unit and pool pump.
FS
Unit is in the defrosting cycle.
(The fan works but the compressor is stopped.)
- -
Keypad is pressing down on both buttons. Replace keypad.
Table A: Control Board Fault Codes
Service Call Verification
Before you make a service call, first determine if the
problem is:
Warranty Service
Unit  operation  (power  supply,  water  flow,  or  time
clock adjustment)
Power Supply
Verify that all circuit breakers are reset and work-
ing properly.
If  the  temperature  display  or  the  Power lamp  on
the  control  panel  still  does  not  light,  contact  the
installing dealer, since it may be a power problem
requiring an electrician.
NOTE: The MANUFACTURER IS NOT RESPON-
SIBLE for these adjustments.
Water Flow
Verify that the pool filter is clean to provide good
flow.
Verify that valves are properly positioned to allow
adequate water flow through the unit.
Time Clock Adjustment
Verify that the time clock is set to permit the unit to run
long enough to heat properly.
11