Dimplex SI 9MER ユーザーズマニュアル

ページ / 29
E-8
English
12
12 Device Information
1
Type and order code 
SI 5MER
SI 7MER
SI 9MER
SI 11MER
2
Design
2.1
Model
Reversible
Reversible
Reversible
Reversible
2.2
Degree of protection according to EN 60 529
 IP20
 IP20
 IP20
 IP20
2.3
Installation location
Indoors
Indoors
Indoors
Indoors
3
Performance data
3.1
Operating temperature limits:
Heating water flow
°C
Up to 55
Up to 55
Up to 55
Up to 55
Cooling, flow
°C
+7 to +20
+7 to +20
+7 to +20
+7 to +20
Brine (heat source, heating)
°C
-5 to +25
-5 to +25
-5 to +25
-5 to +25
Brine (heat sink, cooling)
°C
+5 to +25
+5 to +25
+5 to +25
+5 to +25
Antifreeze
Monoethylene 
glycol
Monoethylene 
glycol
Monoethylene 
glycol
Monoethylene 
glycol
Minimum brine concentration (-13 °C freezing temperature)
25%
25%
25%
25%
3.2
Temperature spread of heating water (flow/return flow) at B0 / W35K
9.4
9.1
10.6
9.9
3.3
Heat output / COP
at B-5 / W55 
1
kW / ---
1. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, both the bivalence point and the regulation should
also be taken into consideration. The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 °C and heating water flow temperature 55 °C.
4.0 / 2.0
5.4 / 2.1
7.5 / 2.0
9.8 / 2.1
at B0 / W50 
1
kW / ---
4.8 / 2.7
6.2 / 2.7
8.8 / 2.8
11.3 / 2.9
at B0 / W35 
1
kW / ---
4.9 / 3.9
6.4 / 3.8
9.3 / 4.0
11.6 / 4.1
3.4
Cooling capacity / COP
at B20 / W8
kW / ---
5.4 / 4.6
7.0 / 4.5
9.9 / 4.6
11.4 / 4.6
at B20 / W18
kW / ---
6.6 / 5.3
8.6 / 5.3
12.0 / 5.4
14.1 / 5.3
at B10 / W8
kW / ---
5.4 / 5.6
7.0 / 5.5
9.9 / 5.6
11.6 / 5.7
at B10 / W18
kW / ---
6.8 / 6.7
8.8 / 6.6
12.4 / 6.7
14.1 / 6.5
3.5
Sound power level
dB(A)
54
55
56
56
3.6
Heating water flow with an internal pressure differential of m³/h / Pa
0.45 / 1,900
0.6 / 3,300
0.75 / 2,300
1.0 / 4,100
3.7
Brine throughput with an internal pressure differential
(heat source) of 
m³/h / Pa
1.2 / 16,000
1.7 / 29,500
2.3 / 25,000
3.0 / 24,000
3.8
Refrigerant; total filling weight
type / kg
R407C / 0.9
R407C / 0.9
R407C / 1.25
R407C / 1.6
4
Dimensions, connections and weight
4.1
Device dimensions without connections 
2
H x W x L mm
2. Note that additional space is required for pipe connections, operation and maintenance.
805 
× 650 × 462 805 × 650 × 462 805 × 650 × 462 805 × 650 × 462
4.2
Device connections to heating system
Inch
G 1¼" external
G 1¼" external
G 1¼" external
G 1¼" external
4.3
Device connections to heat source 
Inch
G 1¼" external
G 1¼" external
G 1¼" external
G 1¼" external
4.4
Weight of the transportable unit(s) incl.  packing
kg
115
117
124
128
5
Electrical Connection
5.1
Nominal voltage; fuse protection
V / A
230 / 16
230 / 16
230 / 20
230 / 25
5.2
Nominal power consumption 
1
 B0 W35
kW
1.25
1.68
2.3
2.8
5.3
Starting current with soft starter
A
24
26
38
38
5.4
Nominal current B0 W35 / cos 
ϕ
A / ---
6.8 / 0.8
9.1 / 0.8
12.5 / 0.8
15.2 / 0.8
6
Complies with the European safety regulations
3
3. See CE declaration of conformity
3
3
3
7
Additional model features
7.1
Water in device protected against freezing 
4
4. The heat circulating pump and the heat pump controller must always be ready for operation.
Yes
Yes
Yes
Yes
7.2
Performance levels
1
1
1
1
7.3
Controller internal/external 
Internal
Internal
Internal
Internal