HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
35
66-2069—02
700AC or 700DC Signal Processor Proof Test Procedure
Equipment
• Powered 700AC or 700DC correctly connected to a 
compatible viewing head.
• Multimeter able to take voltage and resistance 
measurements.
• For 700AC signal processors, an 85V AC to 265V AC 
power source.
• For 700DC signal processors, a 22V DC to 26V DC power 
supply.
• Light source* capable of generating a flame on condition. 
 
* Generally an incandescent bulb will work for IR viewing head 
sensors and a deep UV light or flame will work for UV viewing 
head sensors
Setup
1. Ensure the 700AC or 700DC signal processor under 
test is correctly connected to a compatible viewing head 
and is fully operational.
2. While performing the proof test, disconnect or disregard 
the signal processor outputs so that any outputs due to 
testing do not affect the overall safety system and 
potentially cause a hazardous situation.
3. Record all previously entered user programmable 
settings so that you can restore them to their desired 
values after the proof test.
Tests
1. Remove power to the signal processor and, using a 
multimeter, ensure continuity between ‘SC COM’ and 
‘SC OFF’.
2. Reapply power to the signal processor and, using a 
multimeter, ensure continuity between ‘SC COM’ and 
‘SC ON’.
3. Use a light source to generate a flame on condition and, 
using a multimeter, ensure continuity between ‘RF A 
COM’ and ‘RF A ON’, and between ‘RF B COM’ and ‘RF 
B ON’.
4. Remove any light source to generate a flame off 
condition and, using a multimeter, ensure continuity 
between ‘RF A COM’ and ‘RF A OFF’, and between ‘RF 
B COM’ and ‘RF B OFF’, after the FFRT (Flame Failure 
Response Time) has elapsed.
5. Measure the current draw of the signal processor with 
its viewing head attached and ensure it is less than 
0.07A RMS for 700AC signal processors and 250mA for 
700DC signal processors.
6. Measure the DC voltage between ground ‘VH GND’ and 
‘VH +V’ going to the viewing head. Ensure it is between 
20 and 26 V DC.
7. Change one of the settings of the signal processor and 
store the changed setting. Remove power to the signal 
processor for 10 seconds. Restore power to the signal 
processor and ensure the stored value has remained 
unchanged.
8. Use your light source to generate flamecounts of 
between 12 and 22 on the signal processor. Note the 
flamecount.
a. Increase the gain and store the setting. Ensure the 
flamecount increased.
b. Decrease the gain and store the setting. Ensure the 
flamecount decreased.
9. Restore all original settings as recorded in Setup and 
reconnect the signal processor to the safety system.
Product Decommissioning
When required, decommissioning of the 700 should be 
performed in accordance with requirements of the overall 
safety system.