Electric Heat Amps include electric heater and fan motor current draw. 
 
 
 
265-volt units are to be permanently connected in compliance with National Electrical Code and local codes and have a factory-installed junction box on the chassis.    
 
 
Each 265-volt sub-base kit consists of sub-base with appropriate receptacle for minimum circuit amperage, chaseway to route power connector from sub-base to chassis  
and wiring to connect sub-base to building wiring.  
265-Volt Power Connection Kit must be ordered separately.  
 
 
 
Power Connection Kits
Zoneline
®
 Chassis Nomenclature
The Zoneline chassis is identified by a model number defining the type of unit, cooling capacity, electrical information and 
optional features included on the unit. When specifying or ordering the Zoneline chassis, the use of this nomenclature will 
assure receiving the correct unit.
230/208-Volt Line Cord Connection Units
Line Cord  
Kit
Electric  
Heat  
BTUH
Electric  
Heater  
Watts
Electric  
Heat  
Amps
Min. Circuit 
Protection 
(Amps)
RAK15
8600/7100
2550/2090
11.6/10.6
15
RAK20
11700/9600
450/2820
15.5/14.1
20
RAK0
17100/1900
5000/4090
22./20.
0
Electric Heat Amps include electric heater and fan motor current draw.
Each Line Cord Kit has an integral Leakage Current Detection and  Interruption (LCDI) or Arc Fault 
Current Interrupter (AFCI) device as required by National Electrical Code (NEC) and Underwriters 
Laboratories (UL) for units manufactured after August 1, 2004. 
230/208-Volt Sub-Base and Direct Connected Units
Sub-Base
Direct 
Connection  
Kit
Electric  
Heat  
BTUH
Electric  
Heater  
Watts
Electric  
Heat  
Amps
Min. Circuit 
Protection  
(Amps)
RAK204D15P
RAK4157
8600/7100
2550/2090
11.6/10.6
15
RAK204D20P
RAK4207
11700/9600
450/2820
15.5/14.1
20
RAK204D0P
RAK407
170100/1900 5000/4090 22./20.
0
Electric Heat Amps include electric heater and fan motor current draw.  
Units connected through sub-base do not require a LCDI or AFCI device since they are not 
considered to be line-cord connected. Each 20/208-volt sub-base kit consists of sub-base with 
appropriate receptacle for minimum circuit amperage, chaseway to route power connector from 
sub-base to chassis, wiring to connect sub-base to building wiring and a short line cord with 9-pin 
connector to connect to chassis and plug into receptacle in sub-base. 
Short sub-base line cord may not be used without sub-base. 
Junction box for 20/208-volt chassis must be purchased separately. 
RAK4002A for 2900 and 900 series units RAK4002B for 5800 series units.
265-Volt Sub-Base and Direct Connected Units
Sub-Base
Power 
Connection Kit
Direct  
Connection Kit
Electric Heat 
BTUH
Electric Heater  
Watts
Electric Heat 
Amps
Min. Circuit Protection 
(Amps)
RAK204E15
RAK5172
RAK5157
8600
2550
9.6
15
RAK204E20
RAK5202
RAK5207
11700
450
1.0
20
RAK204E0
RAK502
RAK507
17000
5000
18.9
0
Important
Essential Elements Ordering Overview
20/208-volt line cord connected units — order line cord kit
20/208-volt sub-base connected units — order sub-base and junction box
265-volt units — order sub-base and power connection kit 
EXAMPLE
A
Z
5
8
H
1
2
D
A
D
Chassis series
29= deluxe line cool/
electric heat
9=deluxe line heat pump
58= premium line  
heat pump
Unit type
E= cooling with electric 
resistance heat
H= heat pump with electric 
resistance heat
Zoneline
packaged 
terminal 
chassis
Nominal cooling capacity
07=7,000 BTUH cooling 
09=9,000 BTUH cooling 
12=12,000 BTUH cooling 
15=15,000 BTUH cooling
Special Features
B=base unit
C=corrosion treated
D= internal 
condensate 
removal (ICR)  
system (heat 
pump models 
only) (not for 
coastal areas)
P= Dry Air 25 (2800 
Series only)
Voltage/Phase/
Frequency
D= 20/208-Volt,  
single-phase, 60 Hz
E= 265-Volt, single-phase, 
60 Hz
Universal  