ELECTRONIC CONTROL SEQUENCE OF OPERATION
Compressor and Reversing Valve Control
Cooling
De-Energized
Energized
On
On
Off
Off
Heat - Heat Pump
Heat - Electric
Fan Only
* The Reversing valve stays in the last state until a call for heat or cooling (see figure below)
Compressor Operation:
Cooling Mode
Once the ambient temperature rises past the cool demand threshold (Cool Set Point + 1.5 ˚F) (see figure below), and 
the compressor is not locked out, the cooling cycle begins. As shown in the figure below, the fan is started 5 seconds 
prior to the compressor. Once the ambient temperature has been lowered to the cool set point (Cool Set Point minus 
.25 ˚F), the cooling cycle starts to terminate by shutting off the compressor. After a 30 seconds delay, the fan is shut 
off. (See figure below for graphic details)
The reversing valve only changes when required 
to provide cooling or heat pump. The RV valve 
stays in it's last state until required to change.
Active Mode
Compressor
Reversing Valve State