Single Phase Resistance Test 
Remove the leads from the compressor terminals and set  
the ohmmeter on the lowest scale (R x 1). 
Touch the leads of the ohmmeter from terminals common  
to start (“C” to “S”). Next, touch the leads of the ohmmeter  
from terminals common to run (“C” to “R”).
Add  values  “C”  to  “S”  and  “C”  to  “R”  together  and 
check resistance from start to run terminals (“S” to “R”).  
Resistance “S” to “R” should equal the total of “C” to “S” 
and “C” to “R.”  
In  a  single  phase  PSC  compressor  motor,  the  highest  
value will be from the start to the run connections (“S” to  
“R”). The next highest resistance is from the start to the  
common connections (“S” to “C”). The lowest resistance  
is from the run to common. (“C” to “R”) Before replacing a 
compressor, check to be sure it is defective. 
GROUND TEST
Use  an  ohmmeter  set  on  its  highest  scale.  Touch  one 
lead  to  the  compressor  body  (clean  point  of  contact  as 
a good connection is a must) and the other probe in turn 
to each compressor terminal. If a reading is obtained the 
compressor is grounded and must be replaced.
Check the complete electrical system to the compressor 
and  compressor  internal  electrical  system,  check  to  be 
certain that compressor is not out on internal overload. 
Complete  evaluation  of  the  system  must  be  made 
whenever  you  suspect  the  compressor  is  defective.  If 
the  compressor  has  been  operating  for  sometime,  a 
careful examination must be made to determine why the 
compressor failed.  
Many  compressor  failures  are  caused  by  the  following  
conditions: 
1.    Improper air fl ow over the evaporator. 
2.    Overcharged refrigerant system causing liquid to be
returned to the compressor. 
3.    Restricted refrigerant system. 
4.    Lack of lubrication. 
5.    Liquid refrigerant returning to compressor causing oil 
to be washed out of bearings. 
6.    Noncondensables  such  as  air  and  moisture  in 
          the  system.  Moisture  is  extremely  destructive  to  a
        refrigerant system.
7.     Defective capacitors. 