Friedrich YS13 ユーザーズマニュアル
16
920-198-00
STEP 4
CHECKING WIRING AND PLUMBING: Check all wiring and
plumbing inside and outside of the wall to be sure none will be
broken where the hole is to be cut.
broken where the hole is to be cut.
STEP 5
HOLE CONSTRUCTION: Depending upon size of unit to be
installed, lay out the hole dimensions per the chart below. Cut
and frame in hole to fi nished dimensions. Use 2" x 4" material for
framing and follow the suggested typical installations in Figure
C, D, or E.
and frame in hole to fi nished dimensions. Use 2" x 4" material for
framing and follow the suggested typical installations in Figure
C, D, or E.
NOTE: IF THE WALL CONSTRUCTION IS TYPICAL FRAME
OR 2 x 4 STUDDING WITH BRICK OR STONE VENEERS,
LOCATE THE HOLE NEXT TO ONE OF THE STUDS. FOR
MASONRY, CONCRETE OR CINDER BLOCK WALLS,
LOCATE HOLE FOR CONVENIENCE.
LOCATE THE HOLE NEXT TO ONE OF THE STUDS. FOR
MASONRY, CONCRETE OR CINDER BLOCK WALLS,
LOCATE HOLE FOR CONVENIENCE.
NOTE:
THESE DIMENSIONS ARE FOR FINISHED HOLE SIZE.
FINISHED
DIMENSION
SMALL
CHASSIS
MEDIUM
CHASSIS
LARGE
CHASSIS
A
16
3
⁄
16
"
18
3
⁄
16
"
20
3
⁄
8
"
B
26
3
⁄
16
"
26
3
⁄
16
"
28
1
⁄
4
"
CABINET
CAULK ALL SIDES
ELECTRICAL
RECEPTACLE
(SEE FIG. E FOR
LO CA TION NOTE)
SHIM THE VOID
SPACE AT THE
TOP AND SIDES
WITH WOOD AS
REQUIRED
SPACE AT THE
TOP AND SIDES
WITH WOOD AS
REQUIRED
Figure C
FRAME WALL CONSTRUCTION
CAULK ALL SIDES
CABINET
SHIM VOID SPACES AT TOP AND
SIDES WITH WOOD AS REQUIRED
ELECTRICAL RECEPTACLE
(SEE FIGURE E FOR
LOCATION NOTE)
Figure D
BRICK VENEER CONSTRUCTION
MOR TAR
ELECTRICAL
RE CEP TA CLE
POINT "X"
CABINET
CAULK
ALL SIDES
Figure E
SOLID MASONRY CONSTRUCTION
NOTE:
ELECTRICAL RECEPTACLE LOCATION FROM
POINT "X" MUST BE WITHIN A MAXIMUM RADIUS OF
69" FOR 115V UNITS AND 45" FOR 230V UNITS.
69" FOR 115V UNITS AND 45" FOR 230V UNITS.