eLeCTRICAL TROUBLeshOOTINg ChART - COOLINg
24k BTU
Yes
No
24V at t-stat and
control wiring?
Yes
No
24V at t-stat and
control wiring?
NO COOLING OPERATION
Before continuing 
check for Error 
Codes, see 
electronics control 
diagnostics and 
test mode, page 15
Yes
Yes
Compressor outdoor 
fan motor and indoor 
blower should now 
operate
See Refrigerant Circuit 
diagnosis if unit still is 
not cooling properly
Indoor blower runs but 
outdoor fan motor and 
compressor do not run
Compressor and outdoor 
fan motor run but indoor 
blower does not run
Set thermostat to 
"Cool," move the Temp. 
lever below  the present 
Room Temp.
Nothing operates, 
entire system 
appears dead
Line voltage present 
at the Transformer 
Primary
Problems indicated with 
Room Thermostat or 
Control Wiring
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
O.K.
No
Is Line Voltage present 
at Motor Leads?
Check Capacitor, is 
Capacitor Good?
Replace Capacitor
Motor should run
Possible motor 
problem indicated.  
Check motor 
thoroughly
Yes
Yes
Yes
No
No
No
Supply Circuit 
problems, loose 
Connections, or bad 
Relays/Board
Replace Capacitor 
and/or Start Assist 
Device
Allow ample time 
for pressures to 
equalize
Possible Compressor 
problem indicated.  
See Compressor 
Checks
Is Locked Rotor
Voltage a minimum of 
197 Volts?
Are Capacitor and (if 
so equipped) Start 
Assist good?
Have System 
Pressures Equalized?
Compressor should 
run
Yes
Yes
No
No
No
No
Yes
Compressor and 
outdoor fan motor 
should now operate
See Refrigerant 
Circuit Diagnosis 
if unit still is not 
cooling properly
Yes
Insure that Fuses 
are good and/or that 
Circuit Breakers are 
on and voltage is 208/230
O.K.
208/230 Volts present
at #1 relay and “OD”
terminal on board? 
208/230 Volts present
at compressor’s
contactor?
Problems indicated 
in Blower Relay
of board
Replace board 
Check Supply Circuit’s 
jumper at transformer. If 
okay, replace board
24 Volts at
“R” Terminal on board
24 Volts present at 
Y terminals on
t-stat and board?
Problems indicated with 
Control Transformer
replace board
Defective t-stat
defective control wiring
or transformer
Check contactor
If defective replace
32