1.
2.
3.
4.
5.
ELECTRIC SHOCK HAZARD 
WARNING
Turn off electric power before service or 
installation.
Failure to do so may result in personal injury, 
or death.
Sealed Refrigeration System contains refrigerant 
and oil under high pressure.
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with refrigerants.
Failure  to  follow  these  procedures  could 
result in serious injury or death. 
WARNING
HIGH PRESSURE HAZARD 
The use of nitrogen requires a pressure
regulator. Follow all safety procedures and 
wear protective safety clothing etc. 
Failure to follow proper safety procedures 
result in serious injury or death. 
WARNING
EXPLOSION HAZARD 
Recover all refrigerant and oil from the system.  
 
Remove compressor, capillary tube and filter drier  
from the system.  
 
Flush evaporator condenser and all connecting 
tubing with dry nitrogen or equivalent. Use approved 
flushing agent to remove all contamination from 
system. Inspect suction and discharge line for 
carbon deposits. Remove and clean if necessary. 
Ensure all acid is neutralized. 
 
Reassemble the system, including new drier strainer 
and capillary tube. 
Proceed with step 8-10 on previous page. 
SPECIAL PROCEDURE IN THE CASE OF MOTOR 
COMPRESSOR BURNOUT
ROUTINe MAINTeNANCe
ELECTRICAL SHOCK HAZARD! 
WARNING
Turn  off  electrical  power  before  service  or 
installation. All eletrical connections and wiring 
MUST  be  installed  by  a  qualified  electrician 
and conform to the National Code and all local 
codes which have jurisdiction. Failure to do so 
can result in property damage, personal injury 
and/or death.
To ensure proper unit operation and life expectancy, the 
following maintenance procedures should be performed 
on a regular basis 
1. Air Filter  
To ensure proper unit operation, the air filters should 
be cleaned at least monthly, and more frequently if 
conditions warrant. The unit must be turned off before 
the filters are cleaned. 
To remove the air filters, grasp the top of the filter and lift 
out of the front cabinet.  Reverse the procedure to reinstall 
the filters. 
Clean the filters with a mild detergent in warm water, and 
allow them to dry thoroughly before reinstalling. 
2. Coils & Chassis  
NOTE: Do not use a caustic coil cleaning agent on coils 
or base pan. Use a biodegradable cleaning agent and 
degreaser. The use of harsh cleaning materials may 
lead to deterioration of the aluminum fins or the coil end 
plates. 
The  indoor  coil  and  outdoor  coils  and  base  pan  should 
be  inspected  periodically  (annually  or  semi-annually) 
and  cleaned  of  all  debris  (lint,  dirt,  leaves,  paper,  etc.) 
as necessary. Under extreme conditions, more frequent 
cleaning  may  be  required.    Clean  the  coils  and  base 
pan  with  a  soft  brush  and  compressed  air  or  vacuum.  
A  pressure  washer  may  also  be  used,  however,  you 
must be careful not to bend the aluminum fin pack. Use 
a  sweeping  up  and  down  motion  in  the  direction  of  the 
vertical aluminum fin pack when pressure cleaning coils. 
Note: It is extremely important to insure that none of the 
electrical and/or electronic parts of the unit get wet.  Be 
sure  to  cover  all  electrical  components  to  protect  them 
from water or spray. 
3. Decorative Front  
The decorative front and discharge air grille may be 
cleaned with a mild soap or detergent.  Do NOT use 
solvents or hydrocarbon based cleaners such as 
acetone, naphtha, gasoline, benzene, etc., to clean the 
decorative front or air discharge grilles. 
Use  a  damp  (not  wet)  cloth  when  cleaning  the  control 
area to prevent water from entering the unit, and possibly 
damaging the electronic control 
4. Fan Motor & Compressor  
The fan motor & compressor and are permanently 
lubricated, and require no additional lubrication. 
5. Wall Sleeve 
Inspect the inside of the wall sleeve and drain system 
periodically (annually or semi-annually) and clean as 
required.  Under extreme conditions, more frequent 
cleaning may be necessary.  Clean both of these areas 
with an antibacterial and antifungal cleaner.  Rinse both 
items thoroughly with water and ensure that the drain 
outlets are operating properly.