All installations and services must be performed by qualified service personnel. 
 
 
This procedure can be repeated to determine the airflow for each room in the 
residence. The results of these calculations are given in Table 6, below. 
 
 
Table 6: Required Room Air Flowrates Based on Floor 
Area for Example 2 
Room
Room 
Floor Area 
(Sq. Ft.)
Room Air 
Flowrate 
(CFM)
Number of 
Registers
Flowrate per 
Register 
(CFM)
Living
400
350
3
1 @ 120    
2 @ 115
Dining
120
105
1
105
Kitchen
144
126
1
126
Master 
Bedroom
360
315
2
2 @ 157
Bedroom
224
196
1
196
Bedroom
224
196
1
196
Master 
Bathroom
64
56
1
56
Bathroom
64
56
1
56
Total
1600
1400
11
  
We will assume the airflow is approximately equally split between all registers in 
a particular room. This completes steps (a) through (d) of the duct sizing method. 
 
For step (e), static pressure drops for each system, branch, and component must 
be selected. Since the appliance circulating blower can only tolerate a maximum 
pressure of 0.4 in. W.G., the combined resistance of the supply and return air 
systems cannot exceed this amount.  
64