All installations and services must be performed by qualified service personnel. 
81 
 
DOES FURNACE OPERATE
WITHOUT CONDENSING?
 
IS THE TEMPERATURE
DIFFERENCE BETWEEN SUPPLY
IS STACK TEMPERATURE
Yes
Yes
Yes
Yes
No
No
No
No
IS BURNER SET AS INDICATED
IN ABOVE SECTION?
ADJUST BURNER COMBUSTION
TO PRODUCE ZERO SMOKE.
SLOW THE BLOWER SPEED
TO RAISE TEMPERATURE
RISE.
TROUBLE SHOOTING ENDS.
REPEAT PROCEDURE UNTIL TROUBLE FREE OPERATION IS OBTAINED.
Yes
EFFECTS OF PRESSURE ON NOZZLE FLOW RATE
INCREASE LENGTH OF BURNER ON CYCLE
BY RESETTING BURNER PRIMARY CONTROL
DIP SWITCHES FOR A LONGER OFF  DELAY.
NOZZLE
RATING
AT
100 PSI
NOZZLE
RATING
AT
100 PSI
  NOZZLE FLOW RATES IN
        GALLONS PER HOUR (Approx.)        
     80PSI         120PSI            140PSI         
   NOZZLE FLOW RATES IN
GALLONS PER HOUR (Approx.)
80 PSI        120 PSI       140 PSI
1.35
1.50
1.65
1.75
2.00
2.25
2.50
2.75
3.00
1.21
1.34
1.48
1.57
1.79
2.01
2.21
2.44
2.69
1.48
1.64
1.81
1.92
2.19
2.47
2.74
3.00
3.29
1.60
1.78
1.95
2.07
2.37
2.66
2.96
3.24
3.55
.50
.65
.75
.85
.90
1.00
1.10
1.20
1.25
0.45
0.58
0.67
0.76
0.81
0.89
0.99
1.07
1.12
0.55
0.71
0.82
0.93
0.99
1.10
1.21
1.31
1.37
0.59
0.77
0.89
1.00
1.07
1.18
1.30
1.41
1.48