Diagnostics
The Friedrich Smart Center continuously monitors the PTAC unit 
operation and will store service codes if certain conditions are 
witnessed.  In some cases the unit may take action and shut the 
unit off until conditions are corrected.
To access the error code menu press the ‘Heat’ and ‘High Fan’ 
buttons simultaneously for three seconds. If error codes are 
present they will be displayed. If multiple codes exist you can 
toggle between messages using the temp   button. To clear 
all codes press the temp   button for three seconds while in 
the error code mode. To exit without changing codes press the 
‘Low Fan’ button.
Error 
Code
Code Translation
Action Taken by Unit
Possible Cause
01
NOT USED
NONE
 
02
An extreme low voltage condition 
exists <198V for 230V units and 
<239V for 265V units.
Shut down unit. Display Error code and fl ash.  
Once voltage rises to normal level system power 
is restored.
•  Inadequate power supply
•  Defective breaker
•  Blown fuse
03
Return air thermistor sensor open 
or short circuit
Set return air sensor = 75
°
F.  Alternate fl ash set 
point and error code.  Leave unit running.
•  Defective sensor
04
Indoor coil thermistor sensor open 
Or short circuit
Set ID coil temp = 40
°
F.  Alternate fl ash set point 
and error code.  Leave unit running.
•  Defective sensor
05
Outdoor coil thermistor sensor 
open Or short circuit
Set OD coil temp = 20
°
F.  Alternate fl ash set point 
and error code.  Automatically change over to 
Electric heat Mode only.  Leave unit running.
•  Defective sensor
06
If O.D. coil Temperature > 175 Deg 
F for 2 consecutive minutes. (Heat 
Pump models only)
Alternate fl ash set point and error code. Shut unit 
down for 5 minutes, then try again 2 times, if fails 
the 3rd time, then shut down unit.
•  Dirty coil
•  Fan motor failure
•  Restricted air fl ow
•  Non-condensables in 
refrigeration system
07
I.D coil temperature <30 Deg F for 
2 consecutive minutes.
Alternate fl ash set point and error code.  Continue 
fan operation while the compressor is locked out 
until the indoor coil thermistor reaches 45° F, and 
then energize the compressor. However, com-
pressor must still wait a lockout time of 180 to 240 
seconds.
•  Dirty fi lters
•  Dirty coil
•  Fan motor failure
•  Restricted airfl ow
•  Improper refrigerant charge
•  Restriction in refrigerant circuit
10
Room Freeze Protection triggered
Alternate fl ash set point and error code.  Keep unit 
running.  
•  Room temperature fell below 40°F
Test Mode
For service and diagnostic use only, the built-in timers and 
delays on the PTAC may be bypassed by pressing the ‘Cool’ 
and ‘Low Fan’ buttons simultaneously for three seconds while 
in any mode to enter the test mode. TE will be displayed when 
entering test mode, and DE will be displayed when exiting. The 
test mode will automatically be exited 30 minutes after entering it 
or by pressing the ‘Cool’ and ‘Low Fan’ buttons simultaneously 
for three seconds.
Digital Control Diagnostics and Test Mode
The chart below lists the possible error codes and their description: