Ductless Split Systems
Wall mounted, Tri-zone heat pump
Refrigeration line sets
Insulated line sets are available for all Friedrich split systems in 
15 ft. and 35 ft. lengths. Each line set is equipped with flare nuts 
on both ends. Both liquid and suction lines are insulated. Line 
sets can be joined together with field supplied double female 
connectors. Each system requires one line set for each indoor 
unit installed. On multi-zone systems, line sets should be ordered 
based on individual indoor unit capacities not total system 
capacity.  For example, a M18DYF uses 2 line sets for 9,000 Btu 
units, not 1 for the 18,000 Btu product.
NOTE: All models have low ambient capabilities built-in. Capacity is reduced as 0 degrees Fahrenheit is approached.
NOTE: All R410A models have 1/2˝ UNF 20 thread per inch charging and vacuuming ports. An adapter must be used for 1/4˝ gauges. Adapter part 
number 67270018 is available through Friedrich parts distributors.
Due to continuing research in new energy-saving technology, specifications are subject to change without notice.
Specifications
PERFORMANCE RATINGS
SYSTEM MODEL NO.
M27TYF
M30TYF
M33TYF
M36TYF1
M36TYF2
INDOOR MODEL
3 x MW09Y3FM
2 x MW09Y3FM
MW12Y3FM
MW09Y3FM
2 x MW12Y3FM
2 x MW09Y3FM
MW18Y3FM
3 x MW12Y3FM
OUTDOOR MODEL
MR36TQY3F
MR36TQY3F
MR36TQY3F
MR36TQY3F
MR36TQY3F
CAPACITY COOLING
Btu
9200 ea.
9300 ea.
11800
9400
11800 ea.
9100 ea.
17000
11700 ea.
CAPACITY COOLING MIN - MAx
Btu
5100-11300 ea.
5100-11300 ea.
5100-13600 ea
5100-11300 ea.
5100-13600 ea
5100-11300 ea.
6100-19000 ea.
5100-13600 ea
SENSIBLE HEAT RATIO
0.71
0.71
0.71
0.71
0.71
0.71
0.71
0.71
CAPACITY HEATING @ 47°F
Btu
11200 ea.
11000 ea.
14000
10700
13600 ea.
9800 ea.
18400
12700 ea.
CAPACITY HEATING MIN - MAx
Btu
5100-13000 ea.
5100-13000 ea.
5100-15400 ea.
5100-13000 ea.
5100-15400 ea.
5100-13000 ea.
5500-23000 ea
5100-15400 ea.
CAPACITY HEATING @ 17°F
Btu
8300 ea.
7700 ea.
9800
7200
9200 ea.
6700 ea.
12500
8600 ea.
HSPF
9.0
9.0
9.0
9.0
9.0
SEER
15.0
15.0
15.0
15.0
15.0
EER
10.0
9.2
8.8
8.8
8.8
MOISTURE REMOvAL
Pts/h
2.9 ea.
2.9 ea.
3.7 
2.9 
3.7 ea.
2.9 ea.
5.7 
3.7 ea.
AIRFLOW (QUIET, LOW, MED, HIGH) CFM
185,220,260,295
185,220,260,295 215,250,305,355 185,220,260,295 215,250,305,355 185,220,260,295 240,290,355,415
215,250,305,355
SOUND RATING - INDOOR
dB-A
27,29,33,37
27,29,33,37
30,34,39,42
27,29,33,37
30,34,39,42
27,29,33,37
33,39,42,46
30,34,39,42
SOUND RATING - OUTDOOR
dB-A
52
52
52
52
52
OPERATIONG RANGE (HEATING)
°F
0 - 115 (14 - 75)
0 - 115 (14 - 75)
0 - 115 (14 - 75)
0 - 115 (14 - 75)
0 - 115 (14 - 75)
EST. YEARLY OPERATING COST 
$216
$254
$254
$296
$296
$320
$320
$318
ELECTRICAL DATA (ALL INDOOR UNITS RECEIvE POWER FROM OUTDOOR UNIT; vALUES LISTED ARE TOTAL)
POWER SOURCE
230/(208)-60-1
230/(208)-60-1
230/(208)-60-1
230/(208)-60-1
230/(208)-60-1
MIN. AMPACITY
A
22.5
22.5
22.5
22.5
22.5
COOLING WATTS
W
2710
3180
3710
4000
3980
MAx. TD FUSE/BREAkER
A
30
30
30
30
30
REFRIGERATION SYSTEM
REFRIGERANT
R410A
R410A
R410A
R410A
R410A
COMPRESSOR TYPE
Inverter
Inverter
Inverter
Inverter
Inverter
CONNECTIONS
Flare
Flare
Flare
Flare
Flare
LIQUID LINE O.D.
in
1/4"
1/4"
1/4"
1/4"
1/4"
1/4"
SUCTION LINE O.D.
in
3/8"
3/8"
3/8"
3/8"
1/2"
3/8"
FACTORY PRECHARGE
ft
165'
165'
165'
165'
165'
MAx. LINE LENGTH
ft
Each unit:82  Total:230
Each unit:82  Total:230
Each unit:82  Total:230
Each unit:82  Total:230
Each unit:82Total:230
MAx. HEIGHT DIFFERENCE
ft
49'
49'
49'
49'
49'
DIMENSIONS & WEIGHT
INDOOR UNIT
W x H x D
in 31 1/8" x 10 7/8" x 8 1/2" ea.
31 1/8" x 10 7/8" x 8 1/2" ea.
31 1/8" x 10 7/8" x 8 1/2"
31 1/8" x 10 7/8" x 8 1/2"
31 1/8" x 10 7/8" x 8 1/2"
NET WEIGHT
lbs
21 ea.
21 ea.
21
21
21 ea.
21 ea.
21
21 ea.
SHIPPING WEIGHT
lbs
26 ea.
26 ea.
26
26
26 ea.
26 ea.
26
26 ea.
OUTDOOR UNIT
W x H x D
in
35 3/8" x 32 5/8" x 13"
35 3/8" x 32 5/8" x 13"
35 3/8" x 32 5/8" x 13"
35 3/8" x 32 5/8" x 13"
35 3/8" x 32 5/8" x 13"
NET WEIGHT
lbs
149
149
149
149
149
SHIPPING WEIGHT
lbs
167
167
167
167
167
USED WITH:
LENGTH-FT. LIQUID SUCTION
kIT#
All 9000 and 
12000 Btu
indoor units
15'
1/4”
3/8”
T32150
35'
1/4”
3/8”
T32350
MW18Y3FM 
indoor units
15'
1/4”
1/2”
T42150
35'
1/4”
1/2”
T42350