PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D180
LEGEND
566D180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500
6000
7500
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
80
TC
167.0
177.0
192.0
209.0
183.0
187.0
202.0
219.0
194.0
195.0
208.0
225.0
SHC
167.0
152.0
128.0
104.0
183.0
175.0
146.0
115.0
194.0
193.0
163.0
125.0
kW
13.10
13.40
13.90
14.40
13.60
13.70
14.10
14.70
13.90
13.90
14.30
14.80
85
TC
165.0
174.0
189.0
205.0
180.0
184.0
198.0
214.0
191.0
192.0
204.0
220.0
SHC
165.0
150.0
127.0
102.0
180.0
174.0
145.0
113.0
191.0
191.0
161.0
124.0
kW
13.70
14.00
14.50
15.00
14.20
14.30
14.80
15.30
14.60
14.60
15.00
15.50
95
TC
160.0
167.0
182.0
197.0
174.0
177.0
190.0
206.0
185.0
185.0
196.0
211.0
SHC
160.0
147.0
123.0
99.3
174.0
170.0
141.0
110.0
185.0
185.0
158.0
120.0
kW
14.90
15.20
15.70
16.40
15.50
15.60
16.10
16.70
15.90
15.90
16.30
16.90
100
TC
157.0
164.0
178.0
193.0
171.0
173.0
186.0
202.0
181.0
181.0
191.0
207.0
SHC
157.0
145.0
122.0
97.8
171.0
168.0
140.0
109.0
181.0
181.0
156.0
119.0
kW
15.50
15.80
16.40
17.00
16.10
16.20
16.70
17.40
16.50
16.50
17.00
17.60
105
TC
154.0
160.0
174.0
189.0
168.0
169.0
182.0
197.0
178.0
178.0
187.0
202.0
SHC
154.0
144.0
120.0
96.3
168.0
165.0
138.0
107.0
178.0
178.0
154.0
117.0
kW
16.00
16.30
17.00
17.70
16.70
16.80
17.40
18.10
17.20
17.20
17.60
18.30
115
TC
148.0
153.0
166.0
181.0
162.0
162.0
174.0
188.0
171.0
171.0
178.0
193.0
SHC
148.0
140.0
117.0
93.2
162.0
161.0
135.0
104.0
171.0
171.0
151.0
114.0
kW
17.30
17.50
18.20
19.00
18.00
18.00
18.60
19.40
18.50
18.50
18.90
19.70
566D180/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500
6000
7500
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
80
TC
165.0
175.0
190.0
207.0
180.0
185.0
200.0
217.0
191.0
193.0
206.0
223.0
SHC
165.0
149.0
126.0
102.0
180.0
172.0
143.0
113.0
191.0
190.0
159.0
123.0
kW
13.00
13.30
13.80
14.30
13.50
13.60
14.10
14.60
13.80
13.90
14.30
14.80
85
TC
162.0
171.0
187.0
203.0
177.0
181.0
196.0
213.0
188.0
189.0
202.0
218.0
SHC
162.0
148.0
125.0
101.0
177.0
170.0
142.0
112.0
188.0
187.0
158.0
121.0
kW
13.60
13.90
14.40
15.00
14.10
14.20
14.70
15.30
14.50
14.50
14.90
15.50
95
TC
157.0
165.0
179.0
195.0
171.0
174.0
188.0
204.0
182.0
182.0
193.0
209.0
SHC
157.0
144.0
121.0
97.9
171.0
166.0
139.0
108.0
182.0
181.0
154.0
118.0
kW
14.80
15.10
15.70
16.30
15.30
15.50
16.00
16.60
15.80
15.80
16.20
16.90
100
TC
154.0
161.0
176.0
191.0
168.0
170.0
184.0
199.0
178.0
178.0
189.0
205.0
SHC
154.0
143.0
120.0
96.3
168.0
164.0
137.0
107.0
178.0
178.0
153.0
117.0
kW
15.30
15.70
16.30
17.00
16.00
16.10
16.70
17.30
16.40
16.40
16.90
17.50
105
TC
151.0
158.0
172.0
187.0
165.0
167.0
180.0
195.0
175.0
175.0
185.0
200.0
SHC
151.0
141.0
118.0
94.8
165.0
162.0
135.0
105.0
175.0
175.0
151.0
115.0
kW
15.90
16.20
16.90
17.60
16.60
16.70
17.30
18.00
17.00
17.00
17.50
18.20
115
TC
146.0
151.0
164.0
179.0
159.0
160.0
171.0
186.0
168.0
168.0
176.0
191.0
SHC
146.0
137.0
115.0
91.7
159.0
157.0
132.0
102.0
168.0
168.0
147.0
112.0
kW
17.10
17.40
18.10
18.90
17.80
17.90
18.50
19.30
18.30
18.30
18.80
19.50
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW
— Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC
— Total Capacity (1000 Btuh) Gross
5
0TF
Q00
4
-012
56
6D
/E1
50-
24