Bard F1925 ユーザーズマニュアル

ページ / 5
 
F1925 (2010 08) 
 
 
 
Page 1 of 5 
 
   
 
 
 
 
 
 
 
 
 
BARD MANUFACTURING COMPANY, INC. 
WA Series High Efficiency Air Conditioner 
Engineering Specification Guide 
1.0  GENERAL 
Furnish and install a self-contained, vertical, exterior wall mount,  
through-the-wall air conditioner  to be manufactured by Bard 
Manufacturing Company.  The unit shall be approved and listed by 
Underwriters Laboratories (UL) and Canadian Underwriters Laboratories 
(CUL).  Unit shall be factory assembled, pre-charged, pre-wired, tested and 
ready to operate.  Unit performance shall be certified in accordance with 
the Air Conditioning and Refrigeration Institute Standard 390-2003 for 
Single Package Vertical Units. Units shall be rated by EER.  
EER must be mininum of 10.0. 
Units shall be: 3, 4, 5 ton nominal capacity: 
W38A1- nominal 3 ton capacity,  
W49A1- nominal 4 ton capacity,   
W61A1- nominal 5 ton capacity. 
 
Manufacturers: Capacities shall be as indicated on drawings and units 
shall be manufactured by Bard Manufacturing Company or prior approved 
equal. 
 
2.0  CONSTRUCTION FEATURES 
 
2.1  CABINET 
Construction shall be a single, enclosed, weatherproof casing 
constructed of 20-gauge galvanized steel.  Unit base is constructed 
of 16-gauge galvanized steel.  Each exterior casing panel to be 
bonderized and finished with baked-on exterior polyester enamel 
paint prior to assembly.  The baked-on cured paint finish shall pass 
the industry rub test with a minimum of 72 rubs MEK (Methyl Ethyl 
Ketone) or standard rub test of a minimum of 100 rubs using 
Tolulene.  Cooling section shall be fully insulated with 1-inch 
fiberglass to prevent sweating and to muffle sounds.  Openings shall 
be provided for power connections.  Access openings appropriate 
for outside structure to all fan motors and compressor for making 
repairs and for removing internal components without removing unit 
from its permanent installation. Fresh air intake and outdoor coil 
shall be protected from intrusions by a sturdy metal grating with less 
than 1/4 inch openings. 
 Separate filter service door shall provide easy access for filter 
change, by removing 2 screws on filter access door. No large access 
covers will need to removed.